Parameter
Description
Type
Default
SafePos
Neutral position for control valve:
0 = Closed
1 = Open
2 = Stop
INT
0
SafePosAux
Neutral position for auxiliary
valve:
1= Open
0 = Closed
BOOL
0
SampleTime
Sampling time [s] (assigned auto‐
matically)
REAL
0.1
SelFp1
Call a block saved in this param‐
eter as additional faceplate in
standard view
ANY
-
SelFp2
Call a block saved in this param‐
eter as additional faceplate in pre‐
view
ANY
-
SimLiOp
Activation/deactivation of the sim‐
ulation by:
0 = Operator
1 = Interconnection or SFC
STRUCT
Value: BOOL
ST: BYTE
-
0
16#80
SimOnLi
1 = Simulation via interconnec‐
tion or SFC (controlled by Sim‐
LiOp = 1)
STRUCT
Value: BOOL
ST: BYTE
-
0
16#80
SimOn*
1 = Simulation on
BOOL
0
SimRbk*
Position feedback used for Si‐
mOn = 1
REAL
0.0
SimCnDev
Control Deviation value used for
SimOn = 1
REAL
0.0
SimCnDevLi
Linkable simulation value for Con‐
trol Deviation
STRUCT
Value: BOOL
ST: BYTE
-
0
16#80
SimCurrentTemp
Current Temeprature value used
for SimOn = 1
REAL
0.0
SimCurrentTempLi
Linkable simulation value for Cur‐
rent Temeprature
STRUCT
Value: BOOL
ST: BYTE
-
0
16#80
SimRbkLi
Position feedback used for Si‐
mOnLi.Value = 1 (SimLiOp.Value
=1).
STRUCT
Value: REAL
ST: BYTE
-
0.0
16#80
SlotHart
Number of the slot (channel) with‐
in the AO modules connected to
the Sipart in the HW Config
INT
0
StepNo
Batch step number
DWORD
16#00000000
Tim*
Monitoring time for setting of
"Controller error" fault message
REAL
0.0
SIPART PS2 HART
7.1 SipPS2HA
SITRANS Library for PCS 7
226
Function Manual, 05/2019, A5E35351976-11
Summary of Contents for SITRANS PCS 7
Page 12: ...Table of contents SITRANS Library for PCS 7 12 Function Manual 05 2019 A5E35351976 11 ...
Page 418: ...SITRANS P 10 2 SitraPDr SITRANS Library for PCS 7 418 Function Manual 05 2019 A5E35351976 11 ...
Page 850: ...Index SITRANS Library for PCS 7 850 Function Manual 05 2019 A5E35351976 11 ...