Parameter
Description
Type
Default
UserAna2
Analog auxiliary value 2
STRUCT
● Value : REAL
● ST: BYTE
-
● 0.0
● 16#80
UA2unit
Unit of measure for analog auxiliary val‐
ue 2
INT
0
MsgLock
1 = Suppress process messages.
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
SampleTime
Sampling time [s] (assigned automatical‐
ly)
REAL
0.1
BypLiOp
1 = Bypass commands via interconnec‐
tion
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
BypPVOp
1 = Select bypass PV (via operator)
BOOL
0
RstBypOp
1 = Reset bypass PV (via operator)
BOOL
0
BypPVLi
1 = Select bypass PV (via interconnec‐
tion)
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
RstBypLi
1 = Reset bypass PV (via interconnec‐
tion)
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
BypPV
Substitution value if block is in bypass
STRUCT
● Value : REAL
● ST: BYTE
-
● 0.0
● 16#80
BypLock
1 = Bypass activation or deactivation is
locked for operator
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
SimLiOp
Activation/deactivation of the simulation
by:
0 = Operator
1 = Interconnection or SFC
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
SimOnLi
1 = Simulation via interconnection or
SFC (controlled via
SimLiOp
= 1)
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
SimOn*
1 = Simulation on
BOOL
0
SimPV0*
Process value of the 4 to 20mA signal
that is used for
SimOn
= 1
REAL
0.0
SimPV1*
Process value of the first HART variable
(primary variable) that is used
for
SimOn
= 1
REAL
0.0
SimPV2*
Process value of the second HART vari‐
able (secondary variable) that is used
for
SimOn
= 1
REAL
0.0
SITRANS T
9.1 SitransT
SITRANS Library for PCS 7
334
Function Manual, 05/2019, A5E35351976-11
Summary of Contents for SITRANS PCS 7
Page 12: ...Table of contents SITRANS Library for PCS 7 12 Function Manual 05 2019 A5E35351976 11 ...
Page 418: ...SITRANS P 10 2 SitraPDr SITRANS Library for PCS 7 418 Function Manual 05 2019 A5E35351976 11 ...
Page 850: ...Index SITRANS Library for PCS 7 850 Function Manual 05 2019 A5E35351976 11 ...