Time stamp
This block receives a time stamp value via the
EventTSIn
input parameter. Refer to
"Functions of EventTs" in the APL Online Help.
SIMATIC BATCH functionality
This block provides the standard "SIMATIC BATCH functionality" function that is described in
the APL Online Help.
See also
Mag6T connections (Page 89)
Enabling resetting of commands for the control settings (Page 55)
5.1.4
Mag6T totalizer functions
The functions for this block are listed below.
Totalizer
The block provides the following count modes:
● "Balanced"
● "Positive"
● "Negative"
● "Hold"
Status changes are executed by means of commands of the same name. You may change to
any other state.
Monitoring count limits (Totalizer 1 / Totalizer 2)
You can monitor the high/low alarm and warning limits of the count values:
●
Tot1_AH_Lim
/
Tot2_AH_Lim
: Limit for high alarm
●
Tot1_AL_Lim
/
Tot2_AL_Lim
: Limit for low alarm
●
Tot1_WH_Lim
/
Tot2_WH_Lim
: Limit for high warning
●
Tot1_WL_Lim
/
Tot2_WL_Lim
: Limit for low warning
To clear a limit overshoot/undershoot error, it is necessary to recover the value to hysteresis
limits (Tot1_Hyst/ Tot2_Hyst outputs).
SITRANS F M MAG 6000
5.1 Mag6T
SITRANS Library for PCS 7
Function Manual, 05/2019, A5E35351976-11
79
Summary of Contents for SITRANS PCS 7
Page 12: ...Table of contents SITRANS Library for PCS 7 12 Function Manual 05 2019 A5E35351976 11 ...
Page 418: ...SITRANS P 10 2 SitraPDr SITRANS Library for PCS 7 418 Function Manual 05 2019 A5E35351976 11 ...
Page 850: ...Index SITRANS Library for PCS 7 850 Function Manual 05 2019 A5E35351976 11 ...