Parameter
Description
Type
Default
GradHDnAct
1 = Gradient alarm (low).
1 = Alarm (low) active.
You can change the response for this
parameter by setting Feature bit 28 (de‐
activate switching points) and Feature
bit 29 (high/low signal limit violation) ac‐
cordingly.
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
CmdDosPV2
Current command dosing unit:
● 16#01: Start
● 16#02: Stop
● 16#03: Pause
● 16#04: Resume
● 16#05: Cleaning program
BYTE
16#00
ModeTotPV2
(analog
PV3,PV4)
0 : Totalizer mode
2 : Use preset value
BYTE
16#03
DStr
1 = Start dosing
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
DStp
1 = Stop dosing
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
DPause
1 = Set dosing unit to pause
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
DResume
1 = Resume dosing
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
DActRec
Active dosing recipe (1..5)
BYTE
16#00
DCyclCnt
Dosing cycle counter
DWORD
0
DinputSel
Selection of dosing variable:
0: Mass flow
1: Volume flow
4: Corrected volume flow
5: Fraction A
6: Fraction B
BYTE
0
DCompMode
Compensation mode of dosing unit
BYTE
16#00
DComp
Compensation value of dosing unit
STRUCT
● Value : REAL
● ST: BYTE
-
● 0.0
● 16#80
DSP_Unit
Dosing setpoint unit
INT
0
SITRANS FC430 PA
13.1 SiFC43PA
SITRANS Library for PCS 7
592
Function Manual, 05/2019, A5E35351976-11