Parameter
Description
Type
Default
MV_HiAct
1 = Limit (high) of manipulated var‐
iable violated
STRUCT
Value: BOOL
ST: BYTE
-
0
16#80
MV_LoAct
1 = Limit (low) of manipulated var‐
iable violated
STRUCT
Value: BOOL
ST: BYTE
-
0
16#80
MV_RateTarget
Target manipulated variable for
the gradient limitation
REAL
0.-0
MV_UnitOut
Unit of measure for manipulated
variable
INT
0
OosAct
1 = Block is "Out of service"
STRUCT
Value: BOOL
ST: BYTE
-
0
16#80
Opened
1 = Valve is open
STRUCT
Value: BOOL
ST: BYTE
-
0
16#80
Opening
1 = Valve is opening
STRUCT
Value: BOOL
ST: BYTE
-
0
16#80
OpSt_Out
Value of the input parameter
OpSt_In, for further interconnec‐
tion with other blocks. Bit 31 of this
parameter is used by
Feature
bit
24
DWORD
16#00000000
OS_PermLog
Display of OS_Perm with settings
changed by the block algorithm
DWORD
16#FFFFFFFF
OS_PermOut
Display of OS_Perm
DWORD
16#FFFFFFFF
OS1PermLog
Display of OS1Perm with settings
changed by the block algorithm
DWORD
16#FFFFFFFF
OS1PermOut
Display of OS1Perm
DWORD
16#FFFFFFFF
P_Rst
1= Pulse output for reset
The parameter persists for one cy‐
cle after a reset.
STRUCT
Value: BOOL
ST: BYTE
-
0
16#80
PIExeed_Act
1 = Stoke integral exceeded
(Cbk16)
STRUCT
Value: BOOL
ST: BYTE
-
0
16#80
PosReached
1 = Control valve has reached
specified position
STRUCT
Value: BOOL
ST: BYTE
-
0
16#80
QLim
Response threshold for "controller
error" fault message
STRUCT
Value: REAL
ST: BYTE
-
0.0
16#80
SIPART PS2 PA
8.1 SipPS2PA
SITRANS Library for PCS 7
Function Manual, 05/2019, A5E35351976-11
301