● Operating modes
● Signal status, release for maintenance
● Memo display
● Process value (
PV_In
, 4 to 20 mA signal)
The block icons from template @TemplateAPL_SITRANS.PDL:
Icons
Selection of the block icon in CFC
Configuration in HW Config
1
-
Block icon in the "Out of service"
operating mode
For more information on the block icon and operating options in the block icon, refer to the
following sections in the APL online help:
● "Configuring the block icons"
● "Block icon structure"
● "Operation via the block icon"
10.2
SitraPDr
10.2.1
Description of SitraPDr
Object name (type + number) and family
Type + number: FB 2640
Family: SitransP
Application area of SiFC43Dr
The block is used for the following application:
● Interface block between the technological block SitraPDr and the driver block PiDr64 for
reading and writing acyclic data.
How it works
The SitraPDr block receives requests via its output structures
SxRdReq
and
SxWrReq
to read
data from the device or to write data to the device. Read data or data to be written is transferred
via the
Para
output structure. The AcyclData input structure serves as an interface via which
the read and write jobs are passed on to the PiDr64 driver block.
SITRANS P
10.2 SitraPDr
SITRANS Library for PCS 7
412
Function Manual, 05/2019, A5E35351976-11
Summary of Contents for SITRANS PCS 7
Page 12: ...Table of contents SITRANS Library for PCS 7 12 Function Manual 05 2019 A5E35351976 11 ...
Page 418: ...SITRANS P 10 2 SitraPDr SITRANS Library for PCS 7 418 Function Manual 05 2019 A5E35351976 11 ...
Page 850: ...Index SITRANS Library for PCS 7 850 Function Manual 05 2019 A5E35351976 11 ...