Local operating permission can be set for each specific instance; in other words, block
instances can be enabled or disabled for use on an operator station independently of one
another.
The default setting is 0.
Bit = 0: Disabled
Bit = 1: Enabled
4.24
Suppression of all messages
Feature Bit
Number of the
Feature
bit: 25
Suppression of all messages
You can use this
Feature
bit to determine whether all messages of the block are to be
suppressed.
Bit = 0: Process messages are suppressed.
Bit = 1: All messages are suppressed.
4.25
Disabling operating points
Feature bit
Number of the
Feature
bit: 28
Disabling operating points
You can use this
Feature
bit to define whether the operating point functionality (
xx_Ax_Act/
xx_Wx_Act
outputs) of a limit are also to be deactivated when the message (
MsgLock = 1
)
is deactivated.
The default setting is 0.
Bit = 0: Operating point is not suppressed
Bit = 1: Operating point is suppressed
Configurable response using the Feature I/O
4.25 Disabling operating points
SITRANS Library for PCS 7
Function Manual, 05/2019, A5E35351976-11