(8) Display of second process value (
PV2
) including signal status
This area indicates the current second process value (
PV2
) with the associated signal status.
The name of the configured measured value is displayed depending on the
PV2Meas
tag, in
this case "Distance".
(9) Display of fill time and empty time
Fill time and empty time are shown in this area if
Feature
bit 6 (Activate calculation of fill time/
empty time) is enabled.
With a positive gradient value, a value is calculated for the fill time. With a negative gradient
value, a value is calculated for the empty time.
The calculated times are only shown if the gradient value is outside the deadband
(
DeadTFiEm
).
(10) and (11) Display of auxiliary values
You can use this area to display two auxiliary values that have been configured in the
Engineering System (ES). You can find more information on this in the section "Opening
additional faceplates" in the APL Online Help.
(12) Button for switching to the standard view of any faceplate
Use this button for the standard view of a block configured in the Engineering System (ES). The
visibility of this navigation button depends on the configuration in the engineering system (ES).
You can find more information on this in the section "Opening additional faceplates" in the APL
documentation.
(13), (14) and (15) Display area for block states
This area provides additional information on the operating state of the block:
● "Maintenance"
● "Simulation"
● "Wrong device"
(16) Bar graph for the first "process value" (
PV1
)
This area shows the current first "process value" (
PV1
) in the form of a bar graph. The visible
area in the bar graph depends on the configuration in the engineering system (ES). (see
Display and operating range for process values and limits)
(17) Bar graph for the gradient (process value
PV1
)
This area shows the current gradient value in the form of a bar graph. The visible area in the bar
graph depends on the configuration in the engineering system (ES), see Display and operating
range for process values and limits.
SITRANS LR PA
14.1 SitrLRPA
SITRANS Library for PCS 7
668
Function Manual, 05/2019, A5E35351976-11
Summary of Contents for SITRANS PCS 7
Page 12: ...Table of contents SITRANS Library for PCS 7 12 Function Manual 05 2019 A5E35351976 11 ...
Page 418: ...SITRANS P 10 2 SitraPDr SITRANS Library for PCS 7 418 Function Manual 05 2019 A5E35351976 11 ...
Page 850: ...Index SITRANS Library for PCS 7 850 Function Manual 05 2019 A5E35351976 11 ...