Parameter
Description
Type
Default
DSPLocal
Dosing unit: Setpoint in "Local
mode"
REAL
0.0
LocalSetting
"Local mode" properties (see "Lo‐
cal mode" in the APL Online Help)
INT
0
RstLi
Dosing unit: 1 = Reset interlock
via interconnection
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
RstOp
Dosing unit: 1 = Reset interlock
via operator
BOOL
0
Permit
1 = enable dosing start
0 = no activation enabled on OS
for dosing start
STRUCT
● Value : BOOL
● ST: BYTE
-
● 1
● 16#FF
Perm_En
1 = Activation enable (enable,
Permit parameter) is active
BOOL
1
Intlock
0 = Interlock of the dosing unit
without reset is active; you can
operate the block without reset
once the interlock condition has
been cleared
1 = Interlock of the dosing unit not
activated
STRUCT
● Value : BOOL
● ST: BYTE
-
● 1
● 16#FF
Intl_En
1 = interlock of the dosing unit
without reset (interlock, parame‐
ter Intlock) is active
BOOL
1
Protect
0 = protective interlock of the dos‐
ing unit is active; the block must
be reset once the interlock condi‐
tion has been cleared
1 = Protective interlock of the dos‐
ing unit not activated
STRUCT
● Value : BOOL
● ST: BYTE
-
● 1
● 16#FF
Prot_En
1 = Protective interlock of the dos‐
ing unit (protection, parameter
Protect) is active
BOOL
1
ForceDSrt
Dosing unit: 1 = Force start
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
ForceDStp
Dosing unit: 1 = Force stop
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
ForceDPause
Dosing unit: 1 = Force pause
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
ForceDCont
Dosing unit: 1 = force continue
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
SITRANS F M MAG 6000
5.1 Mag6T
SITRANS Library for PCS 7
Function Manual, 05/2019, A5E35351976-11
99