In/out parameters
Parameter
Description
Type
Default
CyclData
Cyclic data from driver block FbMag6T
(interconnect this input with CyclData
output of FbMag6T)
STRUCT
● CSF : BOOL
● ParaAvail :
WORD
● Input : STRUCT
● Output : STRUCT
AcyclData
Acyclic data from driver block PiDr64 (in‐
terconnect this input with AcyclData out‐
put of PiDr64verschaltet)
STRUCT
● SlotRd : INT
● …
● RetValWr:
WORD
● Input : STRUCT
● Output : STRUCT
● NewDiag : INT
● DiagData :
STRUCT
Output parameters
Parameter
Description
Type
Default
MS_Release
Release for maintenance:
1 = Release for OS operator
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
SetTot1
Totalizer 1: 16#01 = reset command out‐
put to the module (SET_TOT from HW
Config)
BYTE
16#00
ModeTot1
● Totalizer 1: Command transferred to
the module (MODE_TOT from HW
Config)
● 16#00: up counter for positive flow
and down counter for negative flow in
manual mode
● 16#01: Only up counter for positive
flow
● 16#02: Only down counter for
negative flow
● 16#03: Stop totalizer
BYTE
16#03
BypassAct
1 = Bypass is activated in this block
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
SITRANS F M MAG 6000
5.1 Mag6T
SITRANS Library for PCS 7
Function Manual, 05/2019, A5E35351976-11
103
Summary of Contents for SITRANS PCS 7
Page 12: ...Table of contents SITRANS Library for PCS 7 12 Function Manual 05 2019 A5E35351976 11 ...
Page 418: ...SITRANS P 10 2 SitraPDr SITRANS Library for PCS 7 418 Function Manual 05 2019 A5E35351976 11 ...
Page 850: ...Index SITRANS Library for PCS 7 850 Function Manual 05 2019 A5E35351976 11 ...