Status bit
Parameter
25
1 = Control valve has reached intermediate position (STOP)
26
1 = Command for opening the control valve active
27
1 = Command for closing the control valve active
28
1 = Command for stopping the control valve active
29
1 = Runtime error for open control valve
30
1 = Bypass information from preceding function block
31
MS_RelOp
Status word allocation for
Status3
parameter
Status bit
Parameter
0
Effective Signal 1 of the message block interconnected via EventTsIn
1
Effective Signal 2 of the message block interconnected via EventTsIn
2
Effective Signal 3 of the message block interconnected via EventTsIn
3
Effective Signal 4 of the message block interconnected via EventTsIn
4
Effective Signal 5 of the message block interconnected via EventTsIn
5
Effective Signal 6 of the message block interconnected via EventTsIn
6
Effective Signal 7 of the message block interconnected via EventTsIn
7
Effective Signal 8 of the message block interconnected via EventTsIn
8
1 = "Interlock" button is enabled
9
1 = "Permission" button is enabled
10
1 = "Protection" button is enabled
11
1 = Manipulated variable difference high limit violated (ER_AH_Act.Value)
12
1 = Manipulated variable difference low limit violated (ER_AL_Act.Value)
13
1 = Monitor manipulated variable difference high limit (ER_AH_En)
14
1 = Monitor manipulated variable difference low limit (ER_AL_En)
15
1 = Alarm manipulated variable difference high limit violation (ER_AH_MsgEn)
16
1 = Alarm manipulated variable difference low limit violation (ER_AL_MsgEn)
17
1 = Readback value high limit violated (RbkWH_Act.Value)
18
1 = Readback value low limit violated (RbkWL_Act.Value)
19
1 = Monitor readback value high limit (RbkWH_En)
20
1 = Monitor readback value low limit (RbkWL_En)
21
1 = Alarm readback value high limit violation (RbkWH_MsgEn)
22
1 = Alarm readback value low limit violation (RbkWL_MsgEn)
23
1 = Automatic preview control valve "Open"
24
1 = Automatic preview control valve "Closed"
25
1 = Automatic preview control valve "Stop"
26
1 = Show automatic preview in the standard view
27
1 = Auxiliary valve present
28
GrpErr.Value
29
RdyToStart.Value
SIPART PS2 PA
8.1 SipPS2PA
SITRANS Library for PCS 7
264
Function Manual, 05/2019, A5E35351976-11
Summary of Contents for SITRANS PCS 7
Page 12: ...Table of contents SITRANS Library for PCS 7 12 Function Manual 05 2019 A5E35351976 11 ...
Page 418: ...SITRANS P 10 2 SitraPDr SITRANS Library for PCS 7 418 Function Manual 05 2019 A5E35351976 11 ...
Page 850: ...Index SITRANS Library for PCS 7 850 Function Manual 05 2019 A5E35351976 11 ...