Parameter
Description
Type
Default
PV_Meas1
Measurement of Process Value 1:
0: Mass flow
1: Density
2: Process media temperature
5: Volume flow
6: Fraction A
7: Fraction B
8: Fraction A %
9: Fraction B %
10: Corrected volume flow
11: Sensor frame temperature
14: Not used
BYTE
-
PV_Meas2
Measurement of Process Value 2:
0: Mass flow
1: Density
2: Process media temperature
3: Totalizer 1
4: Totalizer 2
5: Volume flow
6: Fraction A
7: Fraction B
8: Fraction A %
9: Fraction B %
10: Corrected volume flow
11: Sensor frame temperature
12: Totalizer 3
13: Control commands
14: Not used
15: Dosing (only PV_Meas2)
BYTE
-
PV_Meas3..4 Measurement of Process Value 3 and 4:
0: Mass flow
1: Density
2: Process media temperature
3: Totalizer 1
4: Totalizer 2
5: Volume flow
6: Fraction A
7: Fraction B
8: Fraction A %
9: Fraction B %
10: Corrected volume flow
11: Sensor frame temperature
12: Totalizer 3
13: Control commands
14: Not used
BYTE
-
LagTime
Delay time [s]
REAL
10.0
DSP_LiOp
Dosing unit: Select setpoint source (internal/
external):
● 1 = Via interconnection
● 0 = Via operator
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
SITRANS FC430 PA
13.1 SiFC43PA
SITRANS Library for PCS 7
566
Function Manual, 05/2019, A5E35351976-11