Output parameters
Parameter
Description
Type
Default
QWronDev
1 = Wrong device connected
BOOL
1
MS_Release
Release for maintenance:
1 = Release for OS operator
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
BypassAct
1 = Bypass is activated in this block
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
PV1_Out1..4
Process value
output
PV1/PV2/PV3/PV4
STRUCT
● Value : REAL
● ST: BYTE
-
● 0.0
● 16#80
PV2PreVal
(analog
PV3,PV4)
Preset value, totalizer
PV2
STRUCT
● Value : REAL
● ST: BYTE
-
● 0.0
● 16#80
PV_Grad
Gradient value for process value
PV1
STRUCT
● Value : REAL
● ST: BYTE
-
● 0.0
● 16#80
PV_GradPP
Gradient value for
PV
1 maximum peak
value
STRUCT
● Value : REAL
● ST: BYTE
-
● 0.0
● 16#80
PV_GradNP
Gradient value for
PV1
minimum peak
value
STRUCT
● Value : REAL
● ST: BYTE
-
● 0.0
● 16#80
GradHUpAct
1 = Gradient alarm (high) for positive
changes.
1 = Alarm (low) active.
You can change the response for this
parameter by setting Feature bit 28 (de‐
activate switching points) and Feature
bit 29 (high/low signal limit violation) ac‐
cordingly.
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
GradHDnAct
1 = Gradient alarm (high) for negative
changes.
1 = Alarm (low) active.
You can change the response for this
parameter by setting Feature bit 28 (de‐
activate switching points) and Feature
bit 29 (high/low signal limit violation) ac‐
cordingly.
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
SITRANS FC430 PA
13.1 SiFC43PA
SITRANS Library for PCS 7
Function Manual, 05/2019, A5E35351976-11
591