Parameter
Description
Type
Default
InLx_WL_Lim*
(x= 1,2,3)
Limit sensor x:
Limit warning (low)
REAL
0.0
InLx_AL_Lim*
(x= 1,2,3)
Limit sensor x:
Alarm limit (low)
REAL
0.0
InLx_Unit*
(x= 1,2,3)
Limit sensor x:
Unit
INT
0
InLx_DevVar*
(x= 1,2,3)
Limit sensor x:
Physical variable
0: Pressure
1: Sensor temperature
2: Electronics temperature
3: Pressure (untrimmed)
4: Fill level
5: Volume
6: Mass
7: Volume flow
8: Mass flow
9: User value
10: Static pressure
11: Not used
BYTE
16#00
Lx_AlmAct*
(x= 1,2,3)
Limit sensor x:
Alarm activation
1: Messages active
BYTE
16#00
Lx_MonAct*
(x= 1,2,3)
Limit sensor x:
Monitoring action
1: Warning
2: Warning and alarm
BYTE
16#00
Lx_MonTrig*
(x= 1,2,3)
Limit sensor x:
Monitoring trigger
1: High limit
2: Low limit
3: High and low limit
BYTE
16#00
Lx_AH_DC*
(x= 1,2,3)
Limit sensor x:
Delay time for incoming alarms with overrange
process value [s]
REAL
0.0
Lx_AH_DG*
(x= 1,2,3)
Limit sensor x:
Delay time for outgoing alarms with overrange
process value [s]
REAL
0.0
Lx_WH_DC*
(x= 1,2,3)
Limit sensor x:
Delay time for incoming warning messages with
overrange process value [s]
REAL
0.0
Lx_WH_DG*
(x= 1,2,3)
Limit sensor x:
Delay time for outgoing warning messages with
overrange process value [s]
REAL
0.0
SITRANS P
10.1 SitransP
SITRANS Library for PCS 7
380
Function Manual, 05/2019, A5E35351976-11