Parameter
Description
Type
Default
MV_ExtLi
Select external manipulated vari‐
able (via interconnection)
STRUCT
Value: BOOL
ST: BYTE
-
0
16#80
MV_ExtOp*
Select external manipulated vari‐
able (via operator)
BOOL
0
MV_Forced
Forced manipulated variable that
is not limited and assumes top
priority
STRUCT
Value: REAL
ST: BYTE
-
0.0
16#80
MV_ForOn
1 = Forced manipulated variable
MV_Forced is output unlimited at
output MV
STRUCT
Value: BOOL
ST: BYTE
-
0
16#80
MV_HiLim
Limit (high) for manipulated vari‐
able MV
REAL
100.0
MV_Int*
Internal manipulated variable
REAL
0.0
MV_IntLi
Select internal manipulated varia‐
ble (via interconnection)
STRUCT
Value: BOOL
ST: BYTE
-
0
16#80
MV_IntOp*
Select internal manipulated varia‐
ble (via operator)
BOOL
1
MV_LiOp
Select manipulated variable
source (internal/external):
1 = Via interconnection
0 = Via operator
STRUCT
Value: BOOL
ST: BYTE
-
0
16#80
MV_LoLim
Limit (low) for manipulated varia‐
ble MV
REAL
0.0
MV_OpScale
OS display range for manipulated
variable MV
STRUCT
High: REAL
Low: REAL
-
100.0
0.0
MV_Trk
Tracking value for manipulated
variable MV
STRUCT
Value: REAL
ST: BYTE
-
0.0
16#80
MV_TrkExt
1 = Bumpless switchover from ex‐
ternal to internal manipulated var‐
iable active
BOOL
0
MV_TrkOn
1 = Tracking of manipulated vari‐
able MV
STRUCT
Value: BOOL
ST: BYTE
-
0
16#80
MV_TrkRbk
1 = Bumpless switchover of ma‐
nipulated variable tracking active
(track manipulated variable to po‐
sition feedback)
BOOL
0
MV_Unit
Unit of measure for manipulated
variable
INT
1342
NoFbkAuxVClose
1 = No "closed" feedback for aux‐
iliary valve present
BOOL
1
SIPART PS2 HART
7.1 SipPS2HA
SITRANS Library for PCS 7
222
Function Manual, 05/2019, A5E35351976-11
Summary of Contents for SITRANS PCS 7
Page 12: ...Table of contents SITRANS Library for PCS 7 12 Function Manual 05 2019 A5E35351976 11 ...
Page 418: ...SITRANS P 10 2 SitraPDr SITRANS Library for PCS 7 418 Function Manual 05 2019 A5E35351976 11 ...
Page 850: ...Index SITRANS Library for PCS 7 850 Function Manual 05 2019 A5E35351976 11 ...