Parameter
Description
Type
Default
AcyclData
Acyclic data from driver block
PiDr256 (interconnect this input
with AcyclData output of PiDr256)
ANY
---
AFct*
Function of alarm module:
0: No function
1: A1=Min. Alarm, A2=Max. Alarm
2: A1=Min. Alarm, A2=Min. Alarm
3: A1=Max. Alarm, A2=Max.
Alarm
4: A1=Min. Alarm, A2=Max.
Alarm (inv)
5: A1=Min. Alarm, A2=Min. Alarm
(inv)
6: A1=Max. Alarm, A2=Max.
Alarm (inv)
BYTE
0
AModFlt
1 = Error message from the Sipart
alarm module
STRUCT
Value: BOOL
ST: BYTE
-
0
16#FF
AutModLi*
1= "Automatic" mode via intercon‐
nection or SFC (controlled via
ModLiOp = 1)
STRUCT
Value: BOOL
ST: BYTE
-
0
16#80
AutModOp*
1 = "Automatic" mode via opera‐
tor (controlled via ModLiOp = 0)
BOOL
0
BatchEn
1 = Enable allocation
BOOL
0
BatchID
Batch ID
DWORD
16#00000000
BatchName
Batch name
S7-String
BE1
Binary input 1 (see Bin1 function) STRUCT
Value: BOOL
ST: BYTE
-
0
16#FF
BE2
Binary input 2 (see Bin2 function) STRUCT
Value: BOOL
ST: BYTE
-
0
16#FF