Parameter
Description
Type
Default
Bin1*
Function of the binary input BE1:
0: No function
1: Message only (NCC)
2: Message only (NOC)
3: Block configuration (NOC)
4: Block configuration and man‐
ual (NOC)
5: Travel valve to position YE
(NOC)
6: Travel valve to position YA
(NOC)
7: Block movement (NOC)
8: Travel valve to position YE
(NCC)
9: Travel valve to position YA
(NCC)
10: Block movement (NCC)
11: Partial stroke test (NOC)
12: Partial stroke test (NCC)
BYTE
0
Bin2*
Function of the binary input BE1:
1: Message only (NCC)
2: Message only (NOC)
3: Travel valve to position YE
(NOC)
4: Travel valve to position YA
(NOC)
5: Block movement (NOC)
6: Travel valve to position YE
(NCC)
7: Travel valve to position YA
(NCC)
8: Block movement (NCC)
9: Partial stroke test (NOC)
10: Partial stroke test (NCC)
BYTE
0
BypProt
1 = Bypassing interlock is active
in "local mode" and in simulation
BOOL
0
Cbk0
1 = Sipart in fail-safe position
STRUCT
Value: BOOL
ST: BYTE
-
0
16#FF
Cbk1
1 = Request for "local operation" STRUCT
Value: BOOL
ST: BYTE
-
0
16#FF
Cbk16
1 = Stroke integral exceeded
STRUCT
Value: BOOL
ST: BYTE
-
0
16#FF
SIPART PS2 HART
7.1 SipPS2HA
SITRANS Library for PCS 7
Function Manual, 05/2019, A5E35351976-11
217