Parameter
Description
Type
Default
FractAP
Current fraction A% value
STRUCT
● Value : REAL
● ST: BYTE
-
● 0.0
● 16#80
FractBP
Current fraction B% value
STRUCT
● Value : REAL
● ST: BYTE
-
● 0.0
● 16#80
CVolFlow
Current corrected volume flow
STRUCT
● Value : REAL
● ST: BYTE
-
● 0.0
● 16#80
SFrTemp
Sensor Frame Temperature
STRUCT
● Value : REAL
● ST: BYTE
-
● 0.0
● 16#80
Tot3
Current totalizer 3 value
STRUCT
● Value : REAL
● ST: BYTE
-
● 0.0
● 16#80
DosQuant
Current dosing quantity
STRUCT
● Value : REAL
● ST: BYTE
-
● 0.0
● 16#80
MflZFSupp
Low flow cut-off suppression (mass flow) STRUCT
● Value : REAL
● ST: BYTE
-
● 0.0
● 16#80
VflZFSupp
Low flow cut-off suppression (volume
flow)
STRUCT
● Value : REAL
● ST: BYTE
-
● 0.0
● 16#80
PV1_AH_Act
(analog
PV2,PV3,PV4)
Limiter
PV1
:
1 = Alarm (high) active.
You can change the response for this
parameter by setting
Feature
bit 28
(deactivate switching points)
and
Feature
bit 29 (high/low signal limit
violation) accordingly.
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
PV1_WH_Act
(analog
PV2,PV3,PV4)
Limiter
PV
1:
1 = Warning (high) active.
You can change the response for this
parameter by setting
Feature
bit 28
(deactivate switching points)
and
Feature
bit 29 (high/low signal limit
violation) accordingly.
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
PV1_WL_Act
(analog
PV2,PV3,PV4)
Limiter
PV1
:
1 = Warning (low) active.
You can change the response for this
parameter by setting
Feature
bit 28
(deactivate switching points)
and
Feature
bit 29 (high/low signal limit
violation) accordingly.
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
SITRANS FC430 PA
13.1 SiFC43PA
SITRANS Library for PCS 7
Function Manual, 05/2019, A5E35351976-11
595
Summary of Contents for SITRANS PCS 7
Page 12: ...Table of contents SITRANS Library for PCS 7 12 Function Manual 05 2019 A5E35351976 11 ...
Page 418: ...SITRANS P 10 2 SitraPDr SITRANS Library for PCS 7 418 Function Manual 05 2019 A5E35351976 11 ...
Page 850: ...Index SITRANS Library for PCS 7 850 Function Manual 05 2019 A5E35351976 11 ...