Text number
Message text
2
Level
3
Distance
14.1.6
I/Os of SitrLRPA
Input parameters
Parameter
Description
Type
Default
PV1
Process value 1
STRUCT
● Value : REAL
● ST: BYTE
-
● 0.0
● 16#FF
PV2
Process value 2
STRUCT
● Value : REAL
● ST: BYTE
-
● 0.0
● 16#FF
PV1Meas*
Measured value that is interconnected at the
PV1
input:
0: <invalid value>
1: Volume
2: Fill level
3: Distance
BYTE
0
PV2Meas*
Measured value that is interconnected at the
PV2
input:
0: <invalid value>
1: Volume
2: Fill level
3: Distance
BYTE
0
Channel1AI*
Channel 1 (read by device)
INT
-1
Channel2AI*
Channel 2 (read by device)
INT
-1
TankType*
Vessel form
BYTE
0
PV1Unit*
Measurement unit for process value 1 (
PV1
)
INT
0
PV2Unit*
Measurement unit for process value 2 (
PV2
)
INT
0
UsrUnit1*
User-specific unit for process value 1 (
PV1
)
S7-String
UsrUnit2*
User-specific unit for process value 2 (
PV2
)
S7-String
InAlgorithm
Echo algorithm
BYTE
16#00
InConfidenc
Echo confidence
BYTE
16#00
InEchoStren
Echo strength
BYTE
16#00
OnOp*
1 = "On" mode via operator
BOOL
0
OosOp*
1 = "Out of service", via OS operator
BOOL
0
OosLi
1 = "Out of service", via interconnection or SFC
(0-1 edge transition)
STRUCT
● Value : BOOL
● ST: BYTE
-
● 0
● 16#80
SITRANS LR PA
14.1 SitrLRPA
SITRANS Library for PCS 7
654
Function Manual, 05/2019, A5E35351976-11