VBA-2E-G11-I/U/PT100-F

VBA-2E-G11-I/U/PT100-V1

AS-Interface Analog Module

FACTORY AUTOMATION

MANUAL

Summary of Contents for VBA-2E-G11-I/U/PT100-F

Page 1: ...A D Spec 2 1 VBA 2E G11 I U PT100 F VBA 2E G11 I U PT100 V1 AS Interface Analog Module FACTORY AUTOMATION MANUAL ...

Page 2: ...s of Delivery for Products and Services of the Electrical Indus try published by the Central Association of the Electrical Industry Zentralverband Elektrotechnik und Elektroindustrie ZVEI e V in its most recent version as well as the supplementary clause Expanded reservation of proprietorship VBA 2E G11 I U PT100 ...

Page 3: ... 10 5 Installation 11 5 1 Storage and transport 11 5 2 Unpacking 11 5 3 Mounting 11 5 4 Connecting the AS Interface 11 5 5 Connecting the Sensors 13 6 Commissioning 14 6 1 Assigning an Address to the Module 14 6 2 Slave Profile 14 6 3 Parameterization 14 7 Troubleshooting 16 7 1 Causes and Elimination of Peripheral Faults 16 7 2 Cause and elimination of a channel fault 16 8 Appendix A 17 8 1 Dimen...

Page 4: ...e the entire range of device functions avoid faulty operation and associated errors reduce costs from downtimes and incidental repairs increase the effectiveness and operating efficiency of your plant Store this operating manual somewhere safe in order to have it available for future work on the device After opening the packaging please ensure that the device is intact and that the package is comp...

Page 5: ...e developed and manufactured under observance of the applicable European standards and guidelines The product manufacturer Pepperl Fuchs GmbH 68307 Mannheim has a certified quality assurance system that conforms to ISO 9001 Note A Declaration of Conformity can be requested from the manufacturer ISO9001 ...

Page 6: ... with the operating manual User modification and or repair are dangerous and will void the warranty and exclude the manufacturer from any liability If serious faults occur stop using the device Secure the device against inadvertent operation In the event of repairs return the device to your local Pepperl Fuchs representative or sales office The connection of the device and maintenance work when li...

Page 7: ... peripheral fault PT1 LED PT2 LED Status of input signal yellow LED Off not active On signal within measurement range Flashing signal outside measurement range I1 LED I2 LED U1 LED U2 LED AUX LED Ext auxiliary power source UAUX dual LED green red Green voltage OK Red voltage reversed INT EXT LED Status indication input supply green LED Green internal input supply Off external input supply INT EXT ...

Page 8: ...e following connections Pt100 inputs functional ground M12 round plug connector Current inputs Voltage inputs Addressing socket Low voltage switch socket 1 3 mm Pt100 inputs functional ground M12 round plug connector Current inputs Voltage inputs AS Interface UAUX 1 AS Interface 2 AUX 3 AS Interface 4 AUX M12 round plug connector 2 T P VBA 2E G11 I U PT100 AUX AS i FAULT R D D A 1 T P I 1 I 2 U 2 ...

Page 9: ...e last detected sensor type is provisionally activated For example the module may not detect which sensor type is connected if the signal values are not within the specified thresholds or if two different sensor types are simultaneously applied to one channel A specific sensor type is finally activated when the signal values measured are within the specified thresholds Note Switching Off the Secon...

Page 10: ...0 measured at 0 C Furthermore as well as other values the mean temperature coefficient of 0 C to 100 C is also defined The mean temperature coefficient defines the mean change in resistance relative to the nominal resistance The analog module calculates the corresponding temperature based on the measured resistance of the temperature sensor Figure 4 5 Curve Pt100 50 100 150 200 250 300 350 400 Res...

Page 11: ... a flat mounting surface by screwing it in place with two M4 mounting screws When the central screw is tightened the functional ground of the M12 round plug connector connects with the metal insert in the mounting base Ensure that this metal insert is connected with the protective ground via the mounting screws The mounting screws are not included Figure 5 1 Screw a blind plug onto unused connecti...

Page 12: ...protection class 1 AS i channel yellow flat cable 2 AUX channel black flat cable 3 Ensure the flat cable is positioned correctly 4 Reattach the upper part of the module 5 Tighten the central screw The recommended tightening torque for this screw is 1 8 Nm The AUX LED and the AS i FAULT LED illuminate in green when the module is connected to the AS Interface and the external auxiliary power source ...

Page 13: ...n examples Pt100 2 wire Pt100 4 wire Current input Voltage input Pt100 input Inputs 3 wire 4 wire 24 V U U 0 V Sig Sig Sig 1 2 4 3 ϑ ϑ I1 I2 U1 U2 PT1 PT2 2 wire 3 wire 4 wire 24 V I I 0 V Sig Sig Sig 1 2 4 3 4 3 1 2 5 4 3 1 2 5 4 3 1 2 5 PT PT 1 2 4 3 Note Connection Instructions Use shielded cables to connect the sensors Note Pin 5 of the M12 round plug connector is the functional ground When th...

Page 14: ...rameters can be set for the VBA 2E G11 I U PT100 Program the parameters using an AS Interface master with the VAZ SW ACT32 AS i Control Tool from Pepperl Fuchs or with the VBP HH1 V3 0 handheld device Parameter P0 50 60 Hz Filter Default value P0 1 active With parameter P0 you activate the filter for 50 60 Hz power frequencies With an activated filter power frequency interference is suppressed In ...

Page 15: ...tivated the AS i FAULT LED flashes in the event of a peripheral fault and a notification is sent to the master A peripheral fault is always reported if The power supply is overloaded The external power supply is not available when the INT EXT switch EXT Parameter P3 Current Input 0 mA 20 mA Default value P3 1 not active Parameter P3 0 is used to set both input channels to current mode Wire break d...

Page 16: ...mination of a channel fault If channel 2 is not transferred and the LED at the connection of the relevant input of channel 2 is not illuminated channel 2 is not activated Cause Solution Sensor supply overload Check sensor supply for short circuit Measured values outside the measurement range Check the connected measurement sensor Pt100 temperature sensor for wire break short circuit Auxiliary powe...

Page 17: ... Flashing green red peripheral fault ANALOG LED Status of input signal yellow LED Off not active On signal within measurement range Flashing signal outside measurement range AUX LED Ext auxiliary power source UAUX dual LED green red Green voltage OK Red voltage reversed INT EXT LED Status indication input supply green LED Green input supply from AS Interface Off input supply from auxiliary power s...

Page 18: ...of temperature displayed C 0 3 C Resolution 16 bit 1 µA current input or 16 bit 1 mV voltage input or 16 bit 0 1 C temperature input Temperature effect Voltage current 20 ppm K Pt100 10 ppm of temperature displayed C 0 003 C K Profile S 7 3 D IO code 7 ID code 3 ID2 code D Data bit function via AS Interface The data value is transmitted as defined by AS Interface profile 7 3 Parameter bit programm...

Page 19: ...on EN 60529 2000 Fieldbus standard EN 50295 1999 IEC 62026 2 2008 Ambient temperature 25 C 70 C 13 F 158 F Storage temperature 25 C 85 C 13 F 185 F Device VBA 2E G11 I U PT100 F VBA 2E G11 I U PT100 V1 Connection AS Interface UAUX insulation piercing technology yellow flat cable black flat cable Inputs M12 round plug connectors AS Interface UAUX M12 round plug connector Inputs M12 round plug conne...

Page 20: ...eripheral fault Table 9 1 Measurement range 1 mA 23 mA 1 Measurement accuracy corresponds to the nominal range Input signal mA Display on the master Input LED 23 32767 Flashing Above threshold peripheral fault 20 001 23 20001 23000 On Extended range 1 0 20 0000 20000 On Nominal range 0 0000 On Below threshold Table 9 2 Measurement range 0 mA 23 mA 1 Measurement accuracy corresponds to the nominal ...

Page 21: ...han the transmission time Latency Conversion time Transmission time Number of channels 1 2 The conversion time is shorter than the transmission time Latency Conversion time Number of channels 1 Transmission time Figure 9 1 Conversion time Transmission time Caution Maximum input voltage The input voltage at the voltage input must not exceed 50 V Input signal V Display on the master Input LED 884 C ...

Page 22: ...idered occupied if one of the following configurations apply A standard address is assigned e g 1 An A or B Address is assigned e g 1A or 1B An A and a B Address are assigned e g 1A and 1B When calculating the cycle time each of these configurations assumed to be one occupied address Cycle time 150 s Number of occupied addresses 2 The transmission time is 7 cycles Transmission time 150 s Number of...

Page 23: ...VBA 2E G11 I U PT100 Appendix B 2014 02 23 ...

Page 24: ...s GmbH 68307 Mannheim Germany Tel 49 621 776 0 E mail info de pepperl fuchs com USA Headquarters Pepperl Fuchs Inc Twinsburg Ohio 44087 USA Tel 1 330 4253555 E mail sales us pepperl fuchs com Asia Pacific Headquarters Pepperl Fuchs Pte Ltd Company Registration No 199003130E Singapore 139942 Tel 65 67799091 E mail sales sg pepperl fuchs com TDOCT2097E_ENG 02 2014 ...