Technical Data
10-24
7SA522 Manual
C53000-G1176-C119-2
Voltage measurement live or bus
30 V to 90 V (phase-to-earth)
(steps 1 V)
Voltage supervision time for
dead / live line or bus
0.10 s to 30.00 s
(steps 0.01 s)
Time delay for close command
transmission
0.00 s to 300 s;
∞
(steps 0.01 s)
10.12 Synchronism and Voltage Check (Dead-line / Dead-bus Check)
Operating Modes
Operating modes
with automatic re-closure
Synchronism check,
dead-line / live-bus
dead-bus / live-line,
dead-bus and dead-line
bypassing or similar combinations of the
above
Synchronism
Closing possible under non-synchronous
system conditions
(with consideration of circuit-breaker
operating time)
Control programs for manual closing
as for automatic reclosure, independently
selectable
Voltages
Minimal operating voltage
1 V
Maximum operating voltage
20 V to 140 V (phase-to-phase)
(steps 1 V)
U> for dead-line / dead-bus check
1 V to 60 V (phase-to-phase)
(steps 1 V)
U< for live-line/ live-bus check
20 V to 125 V (phase-to-phase)
(steps 1 V)
Tolerances
2 % of pick-up value or 2 V
Drop-off to pick-up ratios
approx. 0.9 (U>) or 1.1 (U<)
∆
U-Measurement
Voltage difference
1 V to 40 V (phase-to-phase)
(steps 0.1 V)
Tolerance
1 V
Synchronous
System Conditions
∆ϕ−
measurement
2° to 60°
(steps 1°)
Tolerance
2°
∆
f-measurement
0.03 Hz to 2.00 Hz
(steps 0.01 Hz)
Tolerance
15 mHz
Release delay
0.00 s to 30.00 s
(steps 0.01 s)
Summary of Contents for siprotec 7SA522
Page 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Page 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 620: ...Appendix B 48 ...