Technical Data
10-22
7SA522 Manual
C53000-G1176-C119-2
D
3I0P
(earth)
0.50 s to 15.00 s
(steps 0.01 s)
or
∞
(ineffective)
T
3I0Padd
(earth) 0.00 s to 30.00 s
(steps 0.01 s)
Tolerances
currents
3 % of set value or 1% of nominal current
with definite time
times
1 % of set value or 10 ms
Tolerances currents
Pick-up
at
1.05
≤
I/I
P
≤
1.15;
or 1.05
≤
I/3I
0P
≤
1.15
with inverse time (IEC)
times
5 % ± 15 ms
for 2
≤
I/I
P
≤
20
and T
IP
/s
≥
1;
or 2
≤
I/3I
0P
≤
20
and T
3I0P
/s
≥
1
with inverse time (ANSI) times
5 % ± 15 ms
for 2
≤
I/I
P
≤
20
and D
IP
/s
≥
1;
or 2
≤
I/3I
0P
≤
20
and D
3I0P
/s
≥
1
The set times are pure delay times with definite time protection.
1
) Secondary values based on I
N
= 1 A; for I
N
= 5 A they must be multiplied with 5.
Stub Protection
Overcurrent stage
I
Ph STUB
0.10 A to 25.00 A
1
)
(steps 0.01 A)
T
IPh STUB
0.00 s to 30.00 s
(steps 0.01 s)
or
∞
(ineffective)
3I
0 STUB
>
0.05 A to 25.00 A
1
)
(steps 0.01 A)
T
3I0 STUB
0.00 s to 30.00 s (steps 0.01 s)
or
∞
(ineffective)
Tolerances
currents
3 % of set value or 1% of nominal current
times
1 % of set value or 10 ms
The set times are pure delay times.
1
) Secondary values based on I
N
= 1 A; for I
N
= 5 A they must be multiplied with 5.
Drop-off to Pick-up
Ratios
Current stages
approx. 0.95 for I
P
/I
N
≥
0.5
Summary of Contents for siprotec 7SA522
Page 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Page 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 620: ...Appendix B 48 ...