Appendix
B-12
3148
3I0p Telep/BI
Earth fault overcur-
rent
NO
YES
NO
Instantaneous trip via Teleprot./BI
3149
3I0p SOTF-Trip
Earth fault overcur-
rent
NO
YES
NO
Instantaneous trip after SwitchOnTo-
Fault
3150
3I0p InrushBlk
Earth fault overcur-
rent
NO
YES
NO
Inrush Blocking
3151
IEC Curve
Earth fault overcur-
rent
Normal Inverse
Very Inverse
Extremely Inverse
Long time inverse
Normal Inverse
IEC Curve
3152
ANSI Curve
Earth fault overcur-
rent
Inverse
Short Inverse
Long Inverse
Moderately Inverse
Very Inverse
Extremely Inverse
Definite Inverse
Inverse
ANSI Curve
3153
LOG Curve
Earth fault overcur-
rent
Logarithmic inverse
Logarithmic inverse
LOGARITHMIC Curve
3154
3I0p Startpoint
Earth fault overcur-
rent
1.0..4.0
1.1
Start point of inverse characteristic
3160
POLARIZATION
Earth fault overcur-
rent
with U0 and IY (dual polar-
ized)
with IY (transformer star
point current)
with U2 and I2 (negative
sequence)
with U0 and IY (dual polar-
ized)
Polarization
3162
Dir. ALPHA
Earth fault overcur-
rent
0..360
°
338
°
ALPHA, lower angle for forward direc-
tion
3163
Dir. BETA
Earth fault overcur-
rent
0..360
°
122
°
BETA, upper angle for forward direc-
tion
3164
3U0>
Earth fault overcur-
rent
0.5..10.0 V
0.5 V
Min. zero seq.voltage 3U0 for polariz-
ing
3165
IY>
Earth fault overcur-
rent
0.05..1.00 A
0.05 A
Min. earth current IY for polarizing
3166
3U2>
Earth fault overcur-
rent
0.5..10.0 V
0.5 V
Min. neg. seq. polarizing voltage 3U2
3167
3I2>
Earth fault overcur-
rent
0.05..1.00 A
0.05 A
Min. neg. seq. polarizing current 3I2
3170
2nd InrushRest
Earth fault overcur-
rent
10..45 %
15 %
2nd harmonic ratio for inrush restraint
3171
Imax InrushRest
Earth fault overcur-
rent
0.50..25.00 A
7.50 A
Max.Current, overriding inrush
restraint
3172
SOTF Op. Mode
Earth fault overcur-
rent
with Pickup (non-directional)
with Pickup and direction
with Pickup and direction
Instantaneous mode after Switch-
OnToFault
3173
SOTF Time DELAY Earth fault overcur-
rent
0.00..30.00 sec
0.00 sec
Trip time delay after SOTF
3201
FCT Telep. E/F
Teleprotection for
Earth fault overcurr.
ON
OFF
ON
Teleprotection for Earth Fault O/C
3202
Line Config.
Teleprotection for
Earth fault overcurr.
Two Terminals
Three Terminals
Two Terminals
Line Configuration
3203
Send Prolong.
Teleprotection for
Earth fault overcurr.
0.00..30.00 sec
0.05 sec
Time for send signal prolongation
3207
Delay for alarm
Teleprotection for
Earth fault overcurr.
0.00..30.00 sec
10.00 sec
Unblocking: Time Delay for Alarm
3208
Release Delay
Teleprotection for
Earth fault overcurr.
0.000..30.000 sec
0.000 sec
Time Delay for release after pickup
3209
TrBlk Wait Time
Teleprotection for
Earth fault overcurr.
0.00..30.00 sec
0.04 sec
Transient Block.: Duration external flt.
Addr.
Setting Title
Function
Setting Options
Default Setting
Comments
Summary of Contents for siprotec 7SA522
Page 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Page 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 620: ...Appendix B 48 ...