Functions
6-137
7SA522 Manual
C53000-G1176-C119-2
Figure 6-80 Logic diagram of the stub protection
Switching on to a
Dead Fault
To achieve fast tripping following manual closure of the circuit breaker onto a dead
fault, the switch onto fault signal can be routed to the overcurrent protection. The over-
current protection can then trip three-pole without delay or with a reduced delay. It can
be determined via setting parameter for which stage(s) the rapid tripping following
closure on to a dead fault applies. (Refer also to the logic diagrams in Figure 6-77,
6-78 and 6-80, and Sub-section 6.1.3, margin “Circuit Breaker Status”).
Fault Detection and
Trip Logic
The fault detection signals of the individual phases (and earth) and the individual stag-
es are combined in such a manner that both the phase information as well as the stage
information of the picked up stages can be output. (Table 6-4).
In the case of the trip signals, the stage which resulted in the trip command is also in-
dicated. If the device has the option to trip single-pole, and this option has been acti-
vated, the pole which has been tripped is also indicated during single-pole tripping (re-
fer also to Sub-section 6.17.4 Overall Tripping Logic of the Device).
I
L3
I
L2
I
L1
I
ph
&
7,SK678%
T
0
&
≥
1
Yes
No
,678%627)
Yes
No
,678%7HOHS%,
≥
1
L3
L2
L1
3I
0
&
T
0
&
≥
1
E
7,!678%
I
E
switch onto
fault
T
0
627)7LPH'(/$<
,SK!678%
,!678%
7131 >I-STUB ENABLE
7130 >BLOCK I-STUB
7110 >O/C InstTRIP
I-STUB Trip E
I-STUB Pickup E
I-STUB Trip L3
I-STUB Trip L2
I-STUB Trip L1
I-STUB Pickup L3
I-STUB Pickup L2
I-STUB Pickup L1
Summary of Contents for siprotec 7SA522
Page 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Page 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 620: ...Appendix B 48 ...