Functions
6-129
7SA522 Manual
C53000-G1176-C119-2
6.7.3
Settings
6.7.4
Information Overview
Addr.
Setting Title
Setting Options
Default Setting
Comments
2501
FCT Weak Infeed
OFF
Echo only
Echo and Trip
Echo only
Weak Infeed function is
2502
Trip/Echo DELAY
0.00..30.00 sec
0.04 sec
Trip / Echo Delay after carrier
receipt
2503
Trip EXTENSION
0.00..30.00 sec
0.05 sec
Trip Extension / Echo Impulse
time
2505
UNDERVOLTAGE
2..70 V
25 V
Undervoltage (ph-e)
F.No.
Alarm
Comments
4203
>BLOCK Weak Inf
>BLOCK Weak Infeed Trip function
4221
WeakInf. OFF
Weak Infeed Trip fct. is switched OFF
4222
Weak Inf. BLOCK
Weak Infeed Trip function is BLOCKED
4223
Weak Inf ACTIVE
Weak Infeed Trip function is ACTIVE
4231
WeakInf. PICKUP
Weak Infeed Trip function PICKED UP
4232
W/I Pickup L1
Weak Infeed Trip function PICKUP L1
4233
W/I Pickup L2
Weak Infeed Trip function PICKUP L2
4234
W/I Pickup L3
Weak Infeed Trip function PICKUP L3
4241
WeakInfeed TRIP
Weak Infeed General TRIP command
4242
Weak TRIP 1p.L1
Weak Infeed TRIP command - Only L1
4243
Weak TRIP 1p.L2
Weak Infeed TRIP command - Only L2
4244
Weak TRIP 1p.L3
Weak Infeed TRIP command - Only L3
4245
Weak TRIP L123
Weak Infeed TRIP command L123
4246
ECHO SIGNAL
ECHO Send SIGNAL
Summary of Contents for siprotec 7SA522
Page 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Page 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 620: ...Appendix B 48 ...