Routine Checks and Maintenance
9-10
7SA522 Manual
C53000-G1176-C119-2
o
Carefully pull off the front panel. The front panel is connected to the CPU board with
a short ribbon-cable.
On devices with detached operator panel, the front panel can be pulled off directly
(without a ribbon cable).
S
o
At one end, disconnect the ribbon-cable that links the front panel and the CPU board
(
å
), at the side of the front panel. To disconnect the cable, push up on the top latch of
the plug connector and push down on the bottom latch of the plug connector. Carefully
set aside the front panel.
For the surface mounted device, the 7-pin connector X16 must be disconnected from
the CPU board behind the D-subminiature port, and the ribbon-cable that runs to the
68-pin connector on the back must be detached.
o
Disconnect the ribbon-cable between the CPU board and the I/O board.
o
The boards can be removed and laid on the grounded mat to protect them from ESD
damage.
A greater effort is required to remove the CPU board from the device designed for sur-
face mounting, because of the type of connectors.
Replacing the
Power Supply Fuse
o
Keep ready replacement fuse 5 x 20 mm. Verify the correct rating, correct character-
istic (T) as well as the correct coding.
This data is printed on the module next to the fuse (see Figure 9-5). The type of fuse
depends on the auxiliary supply voltage, e.g. for 24 to 48 VDC the fuse type
“T4H250V” according to IEC 60127–2 is required (refer to Table 9-1). To maintain the
UL–approval, only UL approved fuses may be used (e.g. Messrs. Wickmann. type
181).
o
The I/O module I/O-1, which also incorporates the power supply (in the case of hous-
ing size
1
/
2
slot 19, for housing size
1
/
1
slot 33, refer to Figures 8-7 and 8-8 in Sub-
section 8.1.3) must be removed and placed on a surface suitable for electrostatically
sensitive devices (ESD).
o
Remove the defective fuse. Figure 9-5 illustrates the fuse.
Caution!
Electrostatic discharges through the connections of the components, wiring, and con-
nectors must be avoided! Wearing a grounded wrist strap is preferred. Otherwise, first
touch a grounded metal part.
Warning!
Hazardous voltages may exist in the device, even after the power supply is discon-
nected and the boards are withdrawn from the case! Capacitors can still be charged!
Summary of Contents for siprotec 7SA522
Page 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Page 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 620: ...Appendix B 48 ...