Functions
6-190
7SA522 Manual
C53000-G1176-C119-2
2944 Usyn< U-line>
Sync. dead bus / live line detected
2945 Usyn> U-line<
Sync. live bus / dead line detected
2946 Usyn< U-line<
Sync. dead bus / dead line detected
2947 Sync. Udiff>
Sync. Voltage diff. greater than limit
2948 Sync. fdiff>
Sync. Freq. diff. greater than limit
2949 Sync.
ϕ
-diff>
Sync. Angle diff. greater than limit
2951 Sync. release
Synchronism release (to ext. AR)
2961 Sync.CloseCmd
Close command from synchro-check
2970 Sync. f-bus>>
Sync. Bus frequency > (fn + 3Hz)
2971 Sync. f-bus<<
Sync. Bus frequency < (fn - 3Hz)
2972 Sync. f-line>>
Sync. Line frequency > (fn + 3Hz)
2973 Sync. f-line<<
Sync. Line frequency < (fn - 3Hz)
2974 Sync. U-syn>>
Sync. Bus voltage > Umax (P.3504)
2975 Sync. U-syn<<
Sync. Bus voltage < U> (P.3503)
2976 Sync. U-line>>
Sync. Line voltage > Umax (P.3504)
2977 Sync. U-line>>
Sync. Line voltage < U> (P.3503)