Technical Data
10-13
7SA522 Manual
C53000-G1176-C119-2
10.4
Distance Protection Teleprotection Schemes
Mode
For two line ends
with one channel for each direction or
with three channels for each direction
(for phase segregated transmission)
For three line ends
with one channel for each direction and
oposite line end
Underreach
schemes
Method
Permissive Underreach Transfer Trip
(PUTT) (with overreaching zone Z1B)
Send signal prolongation
0.00 s to 30.00 s
(steps 0.01 s)
Overreach
schemes
Methods
Permissive Overreach Transfer Trip
(POTT) (with overreaching zone Z1B)
Unblocking (with overreaching zone Z1B)
Blocking (with overreaching zone Z1B)
Send signal prolongation
0.00 s to 30.00 s
(steps 0.01 s)
Release signal prolongation
0.000 s to 30.000 s
(steps 0.001 s)
Transient blocking time
0.00 s to 30.00 s
(steps 0.01 s)
Waiting time for transient blocking
0.00 s to 30.00 s;
∞
(steps 0.01 s)
Echo delay time
0.00 s to 30.00 s
(steps 0.01 s)
Echo impulse duration
0.00 s to 30.00 s
(steps 0.01 s)
Time expiry tolerances
1 % of set value or 10 ms
The set times are pure delay times.
Summary of Contents for siprotec 7SA522
Page 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Page 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 620: ...Appendix B 48 ...