Appendix
B-14
3441
U-dead<
Automatic Reclo-
sure
2..70 V
30 V
Voltage threshold for dead line or bus
3450
1.AR: START
Automatic Reclo-
sure
YES
NO
YES
Start of AR allowed in this cycle
3451
1.AR: T-ACTION
Automatic Reclo-
sure
0.01..300.00 sec
0.20 sec
Action time
3452
1.AR 1p allowed
Automatic Reclo-
sure
YES
NO
NO
1pole TRIP allowed
3453
1.AR Tdead 1Flt
Automatic Reclo-
sure
0.01..1800.00 sec
1.20 sec
Dead time after 1phase faults
3454
1.AR Tdead 2Flt
Automatic Reclo-
sure
0.01..1800.00 sec
1.20 sec
Dead time after 2phase faults
3455
1.AR Tdead 3Flt
Automatic Reclo-
sure
0.01..1800.00 sec
0.50 sec
Dead time after 3phase faults
3456
1.AR Tdead1Trip
Automatic Reclo-
sure
0.01..1800.00 sec
1.20 sec
Dead time after 1pole trip
3457
1.AR Tdead3Trip
Automatic Reclo-
sure
0.01..1800.00 sec
0.50 sec
Dead time after 3pole trip
3458
1.AR: Tdead EV.
Automatic Reclo-
sure
0.01..1800.00 sec
1.20 sec
Dead time after evolving fault
3459
1.AR: CB? CLOSE Automatic Reclo-
sure
YES
NO
NO
CB ready interrogation before reclos-
ing
3460
1.AR SynRequest
Automatic Reclo-
sure
YES
NO
NO
Request for synchro-check after 3pole
AR
3461
2.AR: START
Automatic Reclo-
sure
YES
NO
NO
AR start allowed in this cycle
3462
2.AR: T-ACTION
Automatic Reclo-
sure
0.01..300.00 sec
0.20 sec
Action time
3463
2.AR 1p allowed
Automatic Reclo-
sure
YES
NO
NO
1pole TRIP allowed
3464
2.AR Tdead 1Flt
Automatic Reclo-
sure
0.01..1800.00 sec
1.20 sec
Dead time after 1phase faults
3465
2.AR Tdead 2Flt
Automatic Reclo-
sure
0.01..1800.00 sec
1.20 sec
Dead time after 2phase faults
3466
2.AR Tdead 3Flt
Automatic Reclo-
sure
0.01..1800.00 sec
0.50 sec
Dead time after 3phase faults
3467
2.AR Tdead1Trip
Automatic Reclo-
sure
0.01..1800.00 sec
1.20 sec
Dead time after 1pole trip
3468
2.AR Tdead3Trip
Automatic Reclo-
sure
0.01..1800.00 sec
0.50 sec
Dead time after 3pole trip
3469
2.AR: Tdead EV.
Automatic Reclo-
sure
0.01..1800.00 sec
1.20 sec
Dead time after evolving fault
3470
2.AR: CB? CLOSE Automatic Reclo-
sure
YES
NO
NO
CB ready interrogation before reclos-
ing
3471
2.AR SynRequest
Automatic Reclo-
sure
YES
NO
NO
Request for synchro-check after 3pole
AR
3472
3.AR: START
Automatic Reclo-
sure
YES
NO
NO
AR start allowed in this cycle
3473
3.AR: T-ACTION
Automatic Reclo-
sure
0.01..300.00 sec
0.20 sec
Action time
3474
3.AR 1p allowed
Automatic Reclo-
sure
YES
NO
NO
1pole TRIP allowed
3475
3.AR Tdead 1Flt
Automatic Reclo-
sure
0.01..1800.00 sec
1.20 sec
Dead time after 1phase faults
3476
3.AR Tdead 2Flt
Automatic Reclo-
sure
0.01..1800.00 sec
1.20 sec
Dead time after 2phase faults
Addr.
Setting Title
Function
Setting Options
Default Setting
Comments
Summary of Contents for siprotec 7SA522
Page 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Page 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 620: ...Appendix B 48 ...