Functions
6-145
7SA522 Manual
C53000-G1176-C119-2
Stub Protection
When using the I STUB protection the pick-up thresholds
(address
)
and
(address
) are usually not critical, as this protection function is
only activated when the line isolator is open which implies that every measured current
should represents a fault current. With a 1
1
/
2
–circuit breaker arrangement similar to
Figure 6-79 it is possible that large short circuit currents flow from busbar A to busbar
B or to feeder 2 via the current transformers. These currents could cause different
transformation errors in the two current transformer sets
I
A
and
I
B
, especially in the
saturation range. The protection should therefore not be set unnecessarily sensitive.
If the minimum short circuit currents on the busbars are known, the pick-up threshold
is set somewhat (approx. 10 %) below the minimum two phase short cir-
cuit current,
is set below the minimum single-phase current.
The time settings
(address
(address
) are
set to
∞
for this application, to prevent the protection from operating while the line iso-
lator is closed. They may however also be used to implement an independent back-
up stage.
If this stage is applied differently, similar considerations as for the other overcurrent
stages apply.
The parameter
(address
) determines whether the delay
times
(address
) and
(address
) can be
bypassed via a binary input „
!2&,QVW75,3
“. The binary input (if allocated) is
applied to all stages of the time-overcurrent protection. With
=
<(6
you can set the
,6WXE
-stages to trip immediately after the pick-up, only if the
binary input is activated. Set time delays for
12
are always ac-
tivated.
If the
,6WXE
-stage is to trip when switching the line on to a fault with or without a
short delay,
, see above and refer to Sub-section
“General”), the parameter
(address
) is set to
<(6
. If using the
stub protection, then set to
12
as the effect of this protection function only depends on
the position of the isolator.
Summary of Contents for siprotec 7SA522
Page 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Page 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 620: ...Appendix B 48 ...