Functions
6-110
7SA522 Manual
C53000-G1176-C119-2
3131
3I0>
0.003..25.000 A
1.000 A
3I0> Pickup
3132
T 3I0>
0.00..30.00 sec
0.90 sec
T 3I0> Time Delay
3133
NO
YES
NO
Instantaneous trip via Tele-
prot./BI
3134
NO
YES
NO
Instantaneous trip after Swit-
chOnToFault
3135
NO
YES
3140
Op. mode 3I0p
Forward
Reverse
Non-Directional
Inactive
Inactive
Operating mode
3141
3I0p PICKUP
0.05..25.00 A
1.00 A
3I0p Pickup
3141
3I0p PICKUP
0.003..25.000 A
1.000 A
3I0p Pickup
3142 3I0p
MinT-
DELAY
0.00..30.00 sec
1.20 sec
3I0p Minimum Time Delay
3143
3I0p Time Dial
0.05..3.00 sec
0.50 sec
3I0p Time Dial
3144
3I0p Time Dial
0.50..15.00
5.00
3I0p Time Dial
3145
3I0p Time Dial
0.05..15.00 sec
1.35 sec
3I0p Time Dial
3146 3I0p
MaxT-
DELAY
0.00..30.00 sec
5.80 sec
3I0p Maximum Time Delay
3147
Add.T-DELAY
0.00..30.00 sec
1.20 sec
Additional Time Delay
3148
YES
NO
Instantaneous trip via Tele-
prot./BI
3149
NO
YES
NO
Instantaneous trip after Swit-
chOnToFault
3150 3I0p
InrushBlk NO
YES
3151
Normal Inverse
Very Inverse
Extremely Inverse
Long time inverse
Normal Inverse
3152
Inverse
Short Inverse
Long Inverse
Moderately Inverse
Very Inverse
Extremely Inverse
Definite Inverse
Inverse
3153
Logarithmic inverse
Logarithmic inverse LOGARITHMIC Curve
3154
1.0..4.0
1.1
Start point of inverse charac-
teristic
3160
POLARIZATION with Uo and IY (dual polarized)
with IY (transformer star point current)
with U2 and I2 (negative sequence)
with Uo and IY
(dual polarized)
3162
0..360
°
338
°
ALPHA, lower angle for for-
ward direction
Addr.
Setting Title
Setting Options
Default Setting
Comments
Summary of Contents for siprotec 7SA522
Page 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Page 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 620: ...Appendix B 48 ...