Functions
6-217
7SA522 Manual
C53000-G1176-C119-2
Measured Value
Acquisition —
Currents
Four measuring inputs are available in the current circuits. If the three phase currents
and the earth current from the current transformer star-point or from a separate earth
current transformer on the protected circuit are connected to the device, the sum of
the four digitized currents must equal 0. Faults in the current circuits are detected if
I
F
= |
I
L1
+
I
L2
+
I
L3
+ k
I
·
I
E
|
>
I
N
I
max
whereby k
I
(parameter
) takes the eventual ratio difference of a separate
I
E
–current transformer into consideration (e.g. core balance CT). SI THRESHOLD
and SI FACTOR are setting parameters. The amount SI FACTOR ·
I
max
takes the per-
missible current proportional ratio errors of the input transducers into account which
are particularly prevalent during large fault currents (Figure 6-114). The reset ratio is
approx. 97 %.
This failure is alarmed by “Failure
Σ
I”.
Figure 6-114 current sum monitoring
Measured Value
Acquisition —
Voltages
Four measuring inputs are available in the voltage circuits: three for phase–earth volt-
ages as well as one input for the displacement voltage (e-n voltage of an open delta
connection) or a busbar voltage. If the displacement voltage is connected to the de-
vice, the sum of the three digitized phase voltages must equal three times the zero se-
quence voltage. Errors in the voltage transformer circuits are detected when
U
F
= |U
L1
+ U
L2
+ U
L3
+ k
U
· U
EN
|
>
25 V.
The factor k
U
allows for a difference of the transformation ratio between the displace-
ment voltage input and the phase voltage inputs (parameter
reset ratio is approx. 97 %.
This fault is alarmed by “
)DLO
Σ
83K(
”.
Note:
The current sum monitoring is only effective if the fourth current measuring input (
I
4
)
is connected to measure the earth current of the protected line.
I
F
I
N
I
max
I
N
Σ
,7+5(6+2/'
slope:
Σ
,)$&725
Note:
The voltage sum monitoring is only effective if the measuring input for the displace-
ment voltage is connected to a displacement voltage which was generated externally.
Summary of Contents for siprotec 7SA522
Page 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Page 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 620: ...Appendix B 48 ...