Functions
6-64
7SA522 Manual
C53000-G1176-C119-2
to a rapid automatic reclosure. Usually the overreaching zone Z1B is used for the first
cycle (
<HV
). This may be suppressed by changing the setting to
equals
1R
. In this case the overreaching zone Z1B is not released
before and during the 1
st
automatic reclose cycle. Zone Z1 is always released. The
setting only has an effect when the service condition of the automatic reclose function
is input to the device via binary input >Enable ARzones (FNo. 383, power system data
2).