Technical Data
10-20
7SA522 Manual
C53000-G1176-C119-2
10.6
Earth Fault Protection Teleprotection Schemes
Comparison
Schemes
Methods
directional comparison pickup scheme
directional unblocking scheme
directional blocking scheme
Application
2-terminal lines
3-terminal lines
multi-terminal lines via CFC
Send signal prolongation
0.00 s to 30.00 s
(steps 0.01 s)
Release signal prolongation
0.000 s to 30.000 s
(steps 0.001 s)
Transient blocking time
0.00 s to 30.00 s
(steps 0.01 s)
Waiting time for transient blocking
0.00 s to 30.00 s;
∞
(steps 0.01 s)
Echo delay time
0.00 s to 30.00 s
(steps 0.01 s)
Echo impulse duration
0.00 s to30.00 s
(steps 0.01 s)
Time expiry tolerances
1 % of set value or 10 ms
The set times are pure delay times
.
10.7
Weak-Infeed Tripping
Operation method
Phase segregated undervoltage detection after reception of a carrier signal from the
remote end
Undervoltage
Detection
Setting value
U
PhE
<
2 V to 70 V
(steps 1 V)
Drop-out to pick-up ratios
approx. 1.05
Pick-up tolerances
≤
5 % of set value or 0.5 V
Times
Release delay
0.00 s to 30.00 s
(steps 0.01 s)
Release prolongation
0.00 s to 30.00 s
(steps 0.01 s)
Time expiry tolerances
1 % of set value or 10 ms
10.8
External Direct and Remote Tripping
External Trip of the
Local Breaker
Operating time, total
approx. 11 ms
Trip time delay
0.00 s to 30.00 s,
∞
(steps 0.01 s)
Time expiry tolerance
1 % of set value or 10 ms
The set time is a pure delay time.
Summary of Contents for siprotec 7SA522
Page 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Page 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 620: ...Appendix B 48 ...