Configuration
5-29
7SA522 Manual
C53000-G1176-C119-2
Table 5-5
Binary input presettings
Binary Input
LCD Text
Function
No.
Remarks
BI 1
0005
Reset of latched indications, H–active
BI 2
0356
Manual close of the circuit breaker,
H–active
BI 3
0361
7131
Voltage transformer secondary minia-
ture circuit breaker, H–active
Enable I-STUB-Bus function, H–active
BI 4
4006
Distance protection teleprotection re-
ceive signal, H–active
BI 5
) 0381
1
)
single pole trip allowed , H–active
1
)
(others)
—
—
no pre-setting
1
) devices with single- and three-pole tripping
2
) devices with 3-pole tripping
3
) devices with automatic reclosure
Note:
The input
!S7ULS3HUP
(
)1R
) must be activated to achieve single-pole
tripping. The binary input is usually controlled by an external autoreclosure device.
Table 5-6
Output relay presettings
Binary Out-
put
LCD Text
Function No.
Remarks
BO 1
0501
Device (general) pick up
BO 2
4056
Distance protection teleprotection
send signal
BO 3
—
—
no pre-setting
BO 4
2
) 0511
2
)
Device (general) trip command
2
)
1
)
1
)
0512
1
)
0515
1
)
Device (general) trip command for
breaker pole L1
1
)
BO 5
2
) 0511
2
)
Device (general) trip command
2
)
1
)
1
)
0513
1
)
0515
1
)
Device (general) trip command for
breaker pole L2
1
)
BO 6
—
2
) —
2
)
no pre-setting
2
)
1
)
1
)
0514
1
)
0515
1
)
Device (general) trip command for
breaker pole L3
1
)
BO 7
3
)
2851
3
)
Automatic reclosure close command
3
)
1
) devices with single- and three-pole tripping
2
) devices with three-pole tripping only
3
) devices with automatic reclosure
Summary of Contents for siprotec 7SA522
Page 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Page 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 620: ...Appendix B 48 ...