7SA522 Manual
C53000-G1176-C119-2
The computation of the operational measured values is also executed
during an existent system fault in intervals of approx. 0,5 s.
Metering of Energy
The 7SA522 integrates the calculated power which is then made availa-
ble with the “Measured Values”. The components are listed in table 6-10.
The signs (positive = export, negative = import) are defined the same as
for the powers.
Please take into consideration that 7SA522 is, above all, a protection de-
vice. The accuracy of the measured values depends on the current trans-
former (normally protection core) and the tolerances of the device. The
metering is therefore not suited for tarif purposes. The counters can be
reset to zero or any initial value (see Subsubsection 7.1.3.3).
Table 6-9
Operational measured values
Measured values
primary
secondary
% referred to
I
L1
, I
L2
, I
L3
phase currents
A
A
rated operational current
1
)
3I
0
earth currents
A
A
rated operational current
1
)
I
1
, I
2
pos. and neg. seq. currents
A
A
rated operational current
1
)
3I0
sen
sensitive earth current
A
mA
rated operational current
1
)
3
)
I
Y
, I
P
transformer star point current or
earth current in the parallel line
A
A
rated operational current
1
)
3
)
U
L1–L2
, U
L2–L3
, U
L3–L1
line voltages
kV
V
rated operational voltage
2
)
U
L1–E
, U
L2–E
, U
L3–E
phase-earth voltages
kV
V
rated operational voltage
/
√
3
2
)
3U
0
displacement voltage
kV
V
rated operational voltage
·
√
3
2
)
4
)
U
X
voltage at the measuring input U
4
kV
V
rated operational voltage
/
√
3
2
)
U
1
, U
2
pos. and neg. seq. voltages
kV
V
rated operational voltage
/
√
3
2
)
R, X
operational resistance, reactance
Ω
Ω
—
S, P, Q
apparent, real, and reactive power MVA, MW,
MVAR
—
√
3·U
N
·I
N
rated operational values
1
)
2
)
cos
ϕ
power factor
(abs)
(abs)
—
f
frequency
Hz
Hz
rated frequency
1
) acc. to address
(refer to Sub-section 6.1.3)
2
) acc. to address
(refer to Sub-section 6.1.3)
3
) with consideration of the factor
4
) with consideration of the factor
Summary of Contents for siprotec 7SA522
Page 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Page 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 620: ...Appendix B 48 ...