Functions
6-28
7SA522 Manual
C53000-G1176-C119-2
The indicated secondary current values and values of impedance for setting ranges
and default settings refer to I
N
= 1 A. For the nominal current 5 A the current values
are to be multiplied by 5. The values of impedance are divided by 5.
6.1.3.2
Information Overview
1135
Reset Trip CMD
with Pole Open Current
Threshold only
with CBaux AND Pole Open
Current
with Pole Open
Current Threshold
only
RESET of Trip Command
1140
I-CTsat. Thres.
0.2..50.0 A
10.0 A
CT Saturation Threshold
1150
SI Time Man.Cl
0.01..30.00 sec
0.30 sec
Seal-in Time after MANUAL clo-
sures
1151
SYN.MAN.CL
with Synchronism-check
without Synchronism-check
NO
without Synchro-
nism-check
Manual CLOSE COMMAND
generation
1155
3pole coupling
with Pickup
with Trip
with Trip
3 pole coupling
1156
Trip2phFlt 3pole
1pole, leading phase
1pole, lagging phase
3pole
Trip type with 2phase faults
Addr.
Setting Title
Setting Options
Default Setting
Comments
F.No.
Alarm
Comments
351
>CB Aux. L1
>Circuit breaker aux. contact: Pole L1
352
>CB Aux. L2
>Circuit breaker aux. contact: Pole L2
353
>CB Aux. L3
>Circuit breaker aux. contact: Pole L3
379
>CB 3p Closed
>CB aux. contact 3pole Closed
380
>CB 3p Open
>CB aux. contact 3pole Open
356
>Manual Close
>Manual close signal
357
>Close Cmd. Blk
>Block all Close commands from external
361
>FAIL:Feeder VT
>Failure: Feeder VT (MCB tripped)
362
>FAIL:Bus VT
>Failure: Busbar VT (MCB tripped)
366
>CB1 Pole L1
>CB1 Pole L1 (for AR,CB-Test)
367
>CB1 Pole L2
>CB1 Pole L2 (for AR,CB-Test)
368
>CB1 Pole L3
>CB1 Pole L3 (for AR,CB-Test)
410
>CB1 3p Closed
>CB1 aux. 3p Closed (for AR, CB-Test)
411
>CB1 3p Open
>CB1 aux. 3p Open (for AR, CB-Test)
371
>CB1 Ready
>CB1 READY (for AR,CB-Test)
378
>CB faulty
>CB faulty (for Breaker Fail)
381
>1p Trip Perm
>Single-phase trip permitted from ext.AR
Summary of Contents for siprotec 7SA522
Page 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Page 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 620: ...Appendix B 48 ...