Control During Operation
7-14
7SA522 Manual
C53000-G1176-C119-2
From the
Device Front
With a device ready for operation, first press the
key. The
0$,10(18
appears.
Use the
key to select the menu item
0HDVXUHPHQW
, and switch to the list of meas-
ured values using the
key. The
0($685(0(17
selection appears. See figure 7-16.
.
Figure 7-16
Selection of measured values on the front — example
The measured values are divided into the following groups:
01
2SHUDWLRQSUL
Operating measured values, primary.
03
,PSHGDQFH3ULP
Primary operating impedance.
11
2SHUDWLRQVHF
Operating measured values, secondary.
13
,PSHGDQFH6HF
Secondary operating impedance;
Table 7-1
Operational measured values
Measured values
primary
secondary
% referred to
I
L1
, I
L2
, I
L3
phase currents
A
A
rated operational current
1
)
3I
0
earth currents
A
A
rated operational current
1
)
I
1
, I
2
pos. and neg. seq. currents
A
A
rated operational current
1
)
3I0
sen
sensitive earth current
A
mA
rated operational current
1
)
3
)
I
Y
, I
P
transformer star point current or
earth current in the parallel line
A
A
rated operational current
1
)
3
)
U
L1–L2
, U
L2–L3
, U
L3–L1
line voltages
kV
V
rated operational voltage
2
)
U
L1–E
, U
L2–E
, U
L3–E
phase-earth voltages
kV
V
rated operational voltage
/
√
3
2
)
3U
0
displacement voltage
kV
V
rated operational voltage
·
√
3
2
)
4
)
U
X
voltage at the measuring input U
4
kV
V
rated operational voltage
/
√
3
2
)
U
1
, U
2
pos. and neg. seq. voltages
kV
V
rated operational voltage
/
√
3
2
)
R, X
operational resistance, reactance
Ω
Ω
—
S, P, Q
apparent, real, and reactive power MVA, MW,
MVAR
—
√
3· U
N
·I
N
rated operational values
1
)
2
)
cos
ϕ
power factor
(abs)
(abs)
—
f
frequency
Hz
Hz
rated frequency
1
) acc. to address
(refer to Sub-section 6.1.3)
2
) acc. to address
(refer to Sub-section 6.1.3)
3
) with consideration of the factor
4
) with consideration of the factor
MENU
Etc.
0$,10(18
$QQXQFLDWLRQ²!
!
0HDVXUHPHQW²!
0($685(0(17
!
2SHUDWLRQSUL
!
2SHUDWLRQVHF
Summary of Contents for siprotec 7SA522
Page 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Page 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 620: ...Appendix B 48 ...