Control During Operation
7-31
7SA522 Manual
C53000-G1176-C119-2
Figure 7-36
Example: Transfer Block Activated in DIGSI
®
4
Click on
%ORFN'DWD7UDQVPLVVLRQ
to activate or deactivate the transfer block.
After entry of Password No. 4 for test and diagnostics, and confirmation with
2.
, the
setting change is complete.
Activation is indicated with a check mark in front of the command.
Follow the same procedure for the command
7HVW0RGH
, if this option is desired.
Note:
Remember to change the settings for Block Data Transmission and Test Mode back
to the desired, in-service settings (both typically
2))
) when the tests are complete.