Functions
6-111
7SA522 Manual
C53000-G1176-C119-2
The indicated secondary current values for setting ranges and default settings refer to
I
N
= 1 A. For the nominal current 5 A these values are to be multiplied by 5.
3163 Dir.
0..360
°
122
°
BETA, upper angle for forward
direction
3164
0.5..10.0 V
0.5 V
Min. zero seq.voltage 3U0 for
polarizing
3165
0.05..1.00 A
0.05 A
Min. earth current IY for polari-
zing
3166
0.5..10.0 V
0.5 V
Min. neg. seq. polarizing
voltage 3U2
3167
0.05..1.00 A
0.05 A
Min. neg. seq. polarizing cur-
rent 3I2
3170
10..45 %
15 %
2nd harmonic ratio for inrush
restraint
3171
Imax InrushRest 0.50..25.00 A
7.50 A
Max.Current, overriding inrush
restraint
3172
SOTF Op. Mode with Pickup (non-directional)
with Pickup and direction
with Pickup and
direction
Instantaneous mode after
SwitchOnToFault
3173
0.00..30.00 sec
0.00 sec
Addr.
Setting Title
Setting Options
Default Setting
Comments