Appendix
B-3
7SA522 Manual
C53000-G1176-C119-2
140
TripCirc.Superv
Scope of Functions Disabled
1 trip circuit
2 trip circuits
3 trip circuits
Disabled
Trip Circuit Supervision
201
CT Starpoint
Power System Data
1
towards Line
towards Busbar
towards Line
CT Starpoint
203
Unom PRIMARY
Power System Data
1
1.0..1200.0 kV
400.0 kV
Rated Primary Voltage
204
Unom SECOND-
ARY
Power System Data
1
80..125 V
100 V
Rated Secondary Voltage (L-L)
205
CT PRIMARY
Power System Data
1
10..5000 A
1000 A
CT Rated Primary Current
206
CT SECONDARY
Power System Data
1
1A
5A
1A
CT Rated Secondary Current
210
U4 transformer
Power System Data
1
not connected
Udelta transformer
Usync transformer
Ux reference transformer
not connected
U4 voltage transformer is
211
Uph / Udelta
Power System Data
1
0.10..9.99
1.73
Matching ratio Phase-VT To Open-
Delta-VT
212
Usync connect.
Power System Data
1
L1-E
L2-E
L3-E
L1-L2
L2-L3
L3-L1
L1-L2
VT connection for sync. voltage
214
ϕ
Usync-Uline
Power System Data
1
0..360
°
0
°
Angle
adjustment
Usync-Uline
215
U-line / Usync
Power System Data
1
0.80..1.20
1.00
Matching ratio U-line / Usync
220
I4 transformer
Power System Data
1
not connected
Neutral Current (of the pro-
tected line)
Neutral Current of the paral-
lel line
Starpoint Curr. of earthed
power transf.
Neutral Current (of the pro-
tected line)
I4 current transformer is
221
I4/Iph CT
Power System Data
1
0.010..5.000
1.000
Matching ratio I4/Iph for CT’s
230
Rated Frequency
Power System Data
1
50 Hz
60 Hz
50 Hz
Rated Frequency
235
PHASE SEQ.
Power System Data
1
L1 L2 L3
L1 L3 L2
L1
L2
L3 Phase
Sequence
236
Distance Unit
Power System Data
1
km
Miles
km
Distance measurement unit
237
Format Z0/Z1
Power System Data
1
Zero seq. comp. factors RE/
RL and XE/XL
Zero seq. comp. factor K0
and angle(K0)
Zero seq. comp. factors RE/
RL and XE/XL
Setting format for zero seq.comp. for-
mat
239
T-CB close
Power System Data
1
0.01..0.60 sec
0.06 sec
Closing (operating) time of CB
240
TMin TRIP CMD
Power System Data
1
0.02..30.00 sec
0.10 sec
Minimum TRIP Command Duration
241
TMax CLOSE CMD Power System Data
1
0.01..30.00 sec
0.10 sec
Maximum Close Command Duration
242
T-CBtest-dead
Power System Data
1
0.00..30.00 sec
0.10 sec
Dead Time for CB test-autoreclosure
Addr.
Setting Title
Function
Setting Options
Default Setting
Comments
Summary of Contents for siprotec 7SA522
Page 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Page 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 620: ...Appendix B 48 ...