Appendix
B-2
2.1
Settings
Addr.
Setting Title
Function
Setting Options
Default Setting
Comments
103
Grp Chge OPTION
Scope of Functions Disabled
Enabled
Disabled
Setting Group Change Option
110
Trip mode
Scope of Functions 3pole only
1-/3pole
3pole only
Trip mode
112
Phase Distance
Scope of Functions Quadrilateral
MHO
Disabled
Quadrilateral
Phase Distance
113
Earth Distance
Scope of Functions Quadrilateral
MHO
Disabled
Quadrilateral
Earth Distance
120
Power Swing
Scope of Functions Disabled
Enabled
Disabled
Power Swing detection
121
Teleprot. Dist.
Scope of Functions PUTT
POTT
UNBLOCKING
BLOCKING
Disabled
Disabled
Teleprotection for Distance prot.
122
DTT Direct Trip
Scope of Functions Disabled
Enabled
Disabled
DTT Direct Transfer Trip
124
SOTF Overcurr.
Scope of Functions Disabled
Enabled
Disabled
Instantaneous HighSpeed SOTF Over-
current
125
Weak Infeed
Scope of Functions Disabled
Enabled
Disabled
Weak Infeed (Trip and/or Echo)
126
Back-Up O/C
Scope of Functions Disabled
TOC IEC
TOC ANSI
TOC IEC
Backup overcurrent
131
Earth Fault O/C
Scope of Functions Disabled
TOC IEC
TOC ANSI
TOC Logarithm.
Definite Time
Disabled
Earth fault overcurrent
132
Teleprot. E/F
Scope of Functions Dir.Comp.Pickup
UNBLOCKING
BLOCKING
Disabled
Disabled
Teleprotection for Earth fault overcurr.
133
Auto Reclose
Scope of Functions Disabled
1 AR-cycle
2 AR-cycles
3 AR-cycles
4 AR-cycles
5 AR-cycles
6 AR-cycles
7 AR-cycles
8 AR-cycles
ADT
Disabled
Auto-Reclose Function
134
AR control mode
Scope of Functions Pickup w/ Tact
Pickup w/o Tact
Trip w/ Tact
Trip w/o Tact
Pickup w/ Tact
Auto-Reclose control mode
135
Synchro-Check
Scope of Functions Disabled
Enabled
Disabled
Synchronism and Voltage Check
137
Overvoltage
Scope of Functions Disabled
Enabled
Disabled
Overvoltage
138
Fault Locator
Scope of Functions Disabled
Enabled
Enabled
Fault Locator
139
BREAKER FAIL-
URE
Scope of Functions Disabled
Enabled
Disabled
Breaker Failure Protection
Summary of Contents for siprotec 7SA522
Page 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Page 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 620: ...Appendix B 48 ...