Appendix
B-11
7SA522 Manual
C53000-G1176-C119-2
3112
T 3I0>>>
Earth fault overcur-
rent
0.00..30.00 sec
0.30 sec
T 3I0>>> Time delay
3113
3I0>>> Telep/BI
Earth fault overcur-
rent
NO
YES
NO
Instantaneous trip via Teleprot./BI
3114
3I0>>>SOTF-Trip
Earth fault overcur-
rent
NO
YES
NO
Instantaneous trip after SwitchOnTo-
Fault
3115
3I0>>>InrushBlk
Earth fault overcur-
rent
NO
YES
NO Inrush
Blocking
3120
Op. mode 3I0>>
Earth fault overcur-
rent
Forward
Reverse
Non-Directional
Inactive
Inactive
Operating mode
3121
3I0>>
Earth fault overcur-
rent
0.20..25.00 A
2.00 A
3I0>> Pickup
3122
T 3I0>>
Earth fault overcur-
rent
0.00..30.00 sec
0.60 sec
T 3I0>> Time Delay
3123
3I0>> Telep/BI
Earth fault overcur-
rent
NO
YES
NO
Instantaneous trip via Teleprot./BI
3124
3I0>> SOTF-Trip
Earth fault overcur-
rent
NO
YES
NO
Instantaneous trip after SwitchOnTo-
Fault
3125
3I0>> InrushBlk
Earth fault overcur-
rent
NO
YES
NO Inrush
Blocking
3130
Op. mode 3I0>
Earth fault overcur-
rent
Forward
Reverse
Non-Directional
Inactive
Inactive
Operating mode
3131
3I0>
Earth fault overcur-
rent
0.05..25.00 A
1.00 A
3I0> Pickup
3131
3I0>
Earth fault overcur-
rent
0.003..25.000 A
1.000 A
3I0> Pickup
3132
T 3I0>
Earth fault overcur-
rent
0.00..30.00 sec
0.90 sec
T 3I0> Time Delay
3133
3I0> Telep/BI
Earth fault overcur-
rent
NO
YES
NO
Instantaneous trip via Teleprot./BI
3134
3I0> SOTF-Trip
Earth fault overcur-
rent
NO
YES
NO
Instantaneous trip after SwitchOnTo-
Fault
3135
3I0> InrushBlk
Earth fault overcur-
rent
NO
YES
NO Inrush
Blocking
3140
Op. mode 3I0p
Earth fault overcur-
rent
Forward
Reverse
Non-Directional
Inactive
Inactive
Operating mode
3141
3I0p PICKUP
Earth fault overcur-
rent
0.05..25.00 A
1.00 A
3I0p Pickup
3141
3I0p PICKUP
Earth fault overcur-
rent
0.003..25.000 A
1.000 A
3I0p Pickup
3142
3I0p MinT-DELAY
Earth fault overcur-
rent
0.00..30.00 sec
1.20 sec
3I0p Minimum Time Delay
3143
3I0p Time Dial
Earth fault overcur-
rent
0.05..3.00 sec
0.50 sec
3I0p Time Dial
3144
3I0p Time Dial
Earth fault overcur-
rent
0.50..15.00
5.00
3I0p Time Dial
3145
3I0p Time Dial
Earth fault overcur-
rent
0.05..15.00 sec
1.35 sec
3I0p Time Dial
3146
3I0p MaxT-DELAY Earth fault overcur-
rent
0.00..30.00 sec
5.80 sec
3I0p Maximum Time Delay
3147
Add.T-DELAY
Earth fault overcur-
rent
0.00..30.00 sec
1.20 sec
Additional Time Delay
Addr.
Setting Title
Function
Setting Options
Default Setting
Comments
Summary of Contents for siprotec 7SA522
Page 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Page 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 620: ...Appendix B 48 ...