background image

 

R

NTERMATIC

Surge Protection Devices

 

 

CAUTION: 

Turn off power to the electric service or panel and to equipment to be protected 

before installing any Surge Protection Device.  All wiring should be done by a qualified electrician 
and comply with the National Electric Code and local electric codes
.  

 

INSTALLATION 

1. 

Test and verify system voltage to assure proper model selection of Surge Protection Device (SPD).  Refer to the 
wiring configurations and voltages below for additional information. 

2. 

The SPD’s are series devices with a 20-amp maximum.  Verify that a circuit breaker or fuse no larger than 20 
amps protects the circuit. 

3. 

Turn Power OFF. 

4. 

Mount the SPD securely to the panel.  If the unit is positioned outside of the cabinet and prevents the direct 
connection of the nipple to the equipment panel, a short piece of conduit must be used to comply with the national 
Electric Code. 

5. 

Twist or ty-wrap lead wires to eliminate any space or gaps between them.   

6. 

Cut each wire lead to the proper length. DO NOT coil extra wire length. 

7. 

Break the hot (Black) line. Attach the black wire marked “I” to the power source.  Attach the black wire marked “O” 
to the protected equipment lead. 

8. 

Break the neutral (White) line. Attach the white wire marked “I” to the power source.  Attach the white wire marked 
“O” to the protected equipment lead. 

9. 

Connect the GREEN wire lead to the system ground. If the equipment has a separate ground lead, break the 
ground lead and connect the three wires together. 

10. 

Check all connections for proper tightness or torque. Turn Power on. 

11. 

Make sure that the indicator on the SPD is ON. If not, turn power off and recheck each installation step listed 
above.  

12. 

For troubleshooting assistance, call Intermatic at 815-675-7000 and select Technical Assistance from the 
menu. 

 

WIRING CONFIGURATIONS 

 

 

 
 
 
 
 
 
 

  

Installation Instructions 

Models IG1201F20 & IG2401F20 

20 Amp In-Line Protection Device

 

INPUT 

120 VAC Single Phase 
Ground   Neutral   Line 
   Grn       Wht        Blk 

 

PROTECTED 

EQUIPMENT 

Model IG1201F20

 

BLACK (marked I)

 

WHITE (marked I) 

WHITE (marked O) 

BLACK (marked O) 

GREEN GREEN 

INPUT 

240 VAC Single Phase 
Ground   Line 2   Line 1 
   Grn       Blk        Blk 

 

PROTECTED 

EQUIPMENT 

Model IG2401F20

 

GREEN GREEN 

BLACK (marked I)

 

BLACK (marked I)

 

BLACK (marked O)

 

BLACK (marked O)

 

For Din Rail installations use the Din Rail Mounting Plate Kit, part number IG1DIN-F20 