96
Rockwell Automation Publication 2094-UM001D-EN-P - May 2010
Chapter 5
Connecting the Kinetix 6000 Drive System
This example applies to a common-bus follower IAM module.
Figure 48 - IAM Module (IPD connector)
Table 54 - Input Power (IPD) Connections
Table 55 - Termination Specifications
ATTENTION:
Make sure the common-bus power connections are correct
when wiring the IPD connector plug and that the plug is fully engaged in
the module connector. Incorrect wiring/polarity or loose wiring can cause
explosion or damage to equipment.
DC-
DC+
L3
L2
L1
1 2 3 4 5 6
Kinetix 6000
IAM Module, Top View
IPD Connector
(IAM or follower IAM module)
IPD Pin
Signal
6
N.C.
5
N.C.
4
N.C.
3
2
DC+
1
DC-
IMPORTANT
Do not connect three-phase input power to the common-bus follower
IAM module.
IAM Module Cat. No.
Input VAC
Recommended
Wire Size
mm
2
(AWG)
Strip Length
mm (in.)
Torque Value
N•m (lb•in)
2094-AC05-M
xx
-
x
2094-AC09-M02-
x
230V AC
2.5 (14)
10 (0.38)
0.5…0.6
(4.4…5.3)
2094-AC16-M03-
x
10 (8)
16 (0.63)
2.4…3.0
(21.6…26.5)
2094-AC32-M05-
x
25 (4)
2094-BC01-M
xx
-
x
2094-BC02-M02-
x
460V AC
4.0 (12)
10 (0.38)
1.2…1.5
(10.6…13.2)
2094-BC04-M03-
x
10 (8)
16 (0.63)
2.4…3.0
(21.6…26.5)
2094-BC07-M05-
x
25 (4)
Summary of Contents for Allen-Bradley 2094-BC01-M01-S
Page 4: ...4 Rockwell Automation Publication 2094 UM001D EN P May 2010 Summary of Changes Notes...
Page 10: ...10 Rockwell Automation Publication 2094 UM001D EN P May 2010 Table of Contents Notes...
Page 278: ...278 Rockwell Automation Publication 2094 UM001D EN P May 2010 Index Notes...
Page 279: ......