Rockwell Automation Publication 2094-UM001D-EN-P - May 2010
Chapter 2
Planning the Kinetix 6000 Drive System Installation
Table 7 - ControlLogix System Heat Dissipation Example
Figure 5 - ControlLogix Real Power
For backplane power loading requirements of other ControlLogix power
supplies, refer to the ControlLogix Selection Guide, publication
In this example, the amount of power dissipated inside the cabinet is the sum of
the Bulletin 2094 system value (578 W) and the ControlLogix system value
(34 W) for a total of 612 W.
With no active method of heat dissipation (such as fans or air conditioning)
either of these approximate equations can be used.
Enclosure
Component
Description
Backplane Power
Load
(1)
watts
Heat Dissipation
(1)
watts
1756-M08SE
8-axis SERCOS interface module
3.2
0
1756-L5563
L63 ControlLogix processor
4.5
0
1756-IB16D
16 -point input module
0.84
5.8
1756-OB16D
16 -point output module
4.64
3.3
1756-EN
x
T
x
EtherNet/IP communication module
4.0
0
Backplane total
17.18
(2)
N/A
1756-PB72
24V DC ControlLogix power supply
N/A
25
(2)
1756-A7
7-slot mounting chassis
N/A
N/A
Total ControlLogix system wattage
34.1
(1) For ControlLogix module specifications, refer to the ControlLogix Selection Guide, publication
.
(2) Real power heat dissipation is determined by applying the backplane power load (17.18W) to the graph below.
75
60
45
30
15
0
0
20
40
60
80
100
Backplane
Power Load
(watts)
Real Power (watts)
1756-P B72
1756-P B75
DC
Metric
Standard English
Where T is temperature difference between
inside air and outside ambient (°C), Q is heat
generated in enclosure (Watts), and A is
enclosure surface area (m
2
). The exterior surface
of all six sides of an enclosure is calculated as
Where T is temperature difference between
inside air and outside ambient (°F), Q is heat
generated in enclosure (Watts), and A is
enclosure surface area (ft²). The exterior surface
of all six sides of an enclosure is calculated as
A = 2dw + 2dh + 2wh
A = (2dw + 2dh + 2wh) / 144
Where d (depth), w (width), and h (height) are in
meters.
Where d (depth), w (width), and h (height) are in
inches.
A
=
0.38
Q
1.8
T -
1.1
A
=
4.08
Q
T -
1.1
Summary of Contents for Allen-Bradley 2094-BC01-M01-S
Page 4: ...4 Rockwell Automation Publication 2094 UM001D EN P May 2010 Summary of Changes Notes...
Page 10: ...10 Rockwell Automation Publication 2094 UM001D EN P May 2010 Table of Contents Notes...
Page 278: ...278 Rockwell Automation Publication 2094 UM001D EN P May 2010 Index Notes...
Page 279: ......