Rockwell Automation Publication 2094-UM001D-EN-P - May 2010
87
Connecting the Kinetix 6000 Drive System
Chapter
5
Figure 42 - Setting the Ground Jumper (460V Series-A IAM modules)
P13
P14
P12
P13
P14
P12
Bottom Screw
Front Panel (opened)
Ground jumper set
for grounded configuration
(default setting).
Ground jumper set
for ungrounded configuration.
Top Screw
Bottom Screw
Front Panel (opened)
Ground jumper set
for grounded configuration
(default setting).
Ground jumper set
for ungrounded configuration.
Top Screw
2094-BC04-M03-
x
or
2094-BC07-M05-
x
IAM Module (460V)
2094-BC01-MP5-
x
,
2094-BC01-M01-
x
,
or
2094-BC02-M02-
x
IAM Module (460V)
IMPORTANT
Use the default jumper setting or remove the jumper entirely for
grounded power configurations. Move the jumper, as shown above, for
ungrounded power.