Rockwell Automation Publication 2094-UM001D-EN-P - May 2010
105
Connecting the Kinetix 6000 Drive System
Chapter
5
Cable shield and lead preparation is provided with most Allen-Bradley cable
assemblies. Follow these guidelines if your motor power cable shield and wires
require preparation.
Figure 57 - Cable Shield and Lead Preparation
Refer to Axis Module/Rotary Motor Wiring Examples beginning on
for interconnect diagrams.
Table 60 - Motor Power (MP) Connector
Table 61 - Termination Specifications
W
V
U
Motor Power Cable
Exposed Braid
25.4 mm (1.0 in.)
Outer Insulation
105 mm (4.1 in.)
130 mm (5.1 in.)
Strip Length (see table below)
Servo Motor
MP Connector (IAM/AM module)
1326AB (resolver)
All Other Motors
MP Pin
Signal
1 / Black
U / Brown
1
U
2 / Black
V / Black
2
V
3 / Black
W / Blue
3
W
Green/Yellow
Green/Yellow
4
IAM/AM Module
Cat. No.
Recommended
Wire Size
mm
2
(AWG)
Strip Length
mm (in.)
Torque Value
N•m (lb•in)
2094-AC05-M
xx
-
x,
2094-AC09-M02-
x,
2094-BC01-M
xx
-
x
2094-BC02-M02-
x
2094-AMP5-
x
, 2094-AM01-
x
,
2094-AM02-
x
, 2094-BMP5-
x
,
2094-BM01-
x,
and 2094-BM02-
x
Motor power
cable depends on
motor/drive
combination.
6 (10) max
10 (0.38)
0.5…0.6
(4.4…5.3)
2094-AC16-M03-
x
2094-AC32-M05-
x
2094-AM03-
x
, 2094-AM05-
x
1.2…1.5
(10.6…13.2)
2094-BC04-M03-
x
2094-BC07-M05-
x
2094-BM03-
x
, 2094-BM05-
x
25 (4) max
16 (0.63)
2.4…3.0
(21.6…26.5)
Summary of Contents for Allen-Bradley 2094-BC01-M01-S
Page 4: ...4 Rockwell Automation Publication 2094 UM001D EN P May 2010 Summary of Changes Notes...
Page 10: ...10 Rockwell Automation Publication 2094 UM001D EN P May 2010 Table of Contents Notes...
Page 278: ...278 Rockwell Automation Publication 2094 UM001D EN P May 2010 Index Notes...
Page 279: ......