Rockwell Automation Publication 2094-UM001D-EN-P - May 2010
231
Upgrading the Kinetix 6000 Drive Firmware
Appendix C
Configure Logix Communication
This procedure assumes that your communication method to the Logix
controller is using the Ethernet protocol. It is also assumed that your Logix
Ethernet module has already been configured.
For more information, refer to the ControlLogix System User Manual,
publication
.
Follow these steps to configure Logix communication.
1.
Open your RSLinx Classic software.
2.
From the Communications pull-down menu, choose Configure Drivers.
The Configure Drivers dialog box opens.
3.
From the Available Drive Types pull-down menu, choose Ethernet devices.
4.
Click Add New.
The Add New RSLinx Classic Driver dialog box opens.
5.
Type the new driver name.
6.
Click OK.