6 Flow meters
Manual ERZ 2000-NG · EN07 · 2019, May 13th
254
Coordinates AP53 to AP58 are provided for inclusion of sensor data (manufacturer,
type plate, etc.)
Note
For the optimal operating mode of the ERZ2000-NG as an orifice flow me-
ter, the second A/D converter available in the device is commissioned in
order to ensure a quick delta-p measurement in parallel to the measure-
ment of pressure and temperature.
For this purpose, the user must switch to
chapter 3.1.7.1 Inputs
(current
inputs) of the selected channel and the parameter measuring strategy
must be set to effective pressure (attention: access reserved for super us-
ers only).
Example:
Current input 4 should measure the small cell
=> Chapter ND Current input 4 terminal X6-1, X6-2
Coordinate ND09
includes the parameter
Measuring strategy
. The parameter for
the flow computer operation is set to standard by default. Please set this parameter
to
diff. pressure
for orifice plate flow computers. This setting must be repeated for all
current inputs which are selected for delta-p measuring cells.
Please operate the inputs for pressure and temperature, and/or all measuring cells
which are not used for delta-p on
standard
.
Refer to the relevant notices for the pressure transducer for activation of the HART
operating mode of the delta-p transducer.
Summary of Contents for ERZ2000-NG
Page 10: ......
Page 68: ...2 Introduction Manual ERZ 2000 NG EN07 2019 May 13th 58 Figure 44 Menu LA Overview...
Page 69: ...2 Introduction Manual ERZ 2000 NG EN07 2019 May 13th 59 Figure 45 Menu LB Totalizer BM1...
Page 77: ...2 Introduction Manual ERZ 2000 NG EN07 2019 May 13th 67 Figure 51 Overview System sub menu...
Page 241: ...6 Flow meters Manual ERZ 2000 NG EN07 2019 May 13th 231 Figure 167 Interface module C34...
Page 340: ...8 Overview Coordinates Manual ERZ 2000 NG EN07 2019 May 13th 330 8 5 6 TSV export...
Page 453: ...Certificates Manual ERZ 2000 NG EN07 2019 May 13th 443...